L5: fault restart, L6: torque detection – Yaskawa Z1000U User Manual

Page 292

background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L4-04

(049C)

Speed Agreement

Detection Width

(+/-)

Spd Agree Wdth+-

Sets the hysteresis or allowable margin for speed detection.

Default: 2.0 kHz

Min.: 0.0

Max.: 20.0

L4-05

(049D)

Frequency Reference

Loss Detection

Selection

Ref Loss Sel

0: Stop

1: Run@L4-06PrevRef

0: Stop. Drive stops when the frequency reference is lost.

1: Run. Drive runs at a reduced speed when the frequency

reference is lost.

Default: 1

Range: 0, 1

126

L4-06

(04C2)

Frequency Reference

at Reference Loss

Fref at Floss

Sets the percentage of the frequency reference that the drive

should run with when the frequency reference is lost.

Default: 80.0%

Min.: 0.0

Max.: 100.0

127

L4-07

(0470)

Speed Agreement

Detection Selection

Freq Detect Sel

0: No Detection @BB

1: Always Detected

0: No detection during baseblock.

1: Detection always enabled.

Default: 0

Range: 0, 1

u

L5: Fault Restart

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L5-01

(049E)

Number of Auto Restart

Attempts

Num of Restarts

Sets the number of times the drive may attempt to restart after

the following faults occur: GF, LF, oC, ov, PF, oL1, oL2, oL3,

STo, Uv1.

Default: 0

Min.: 0

Max.: 10

127

L5-02

(049F)

Auto Restart Fault

Output Operation

Selection

Restart Sel

0: Flt Outp Disabld

1: Flt Outp Enabled

0: Fault output not active.

1: Fault output active during restart attempt.

Default: 0

Range: 0, 1

167

L5-03

(04A0)

Time to Continue

Making Fault Restarts

Max Restart Time

Enabled only when L5-05 is set to 0. Causes a fault if a fault

restart cannot occur after the set time passes.

Default: 180.0 s

Min.: 0.1

Max.: 600.0

127

L5-04

(046C)

Fault Reset Interval

Time

Flt Reset Wait T

Sets the amount of time to wait between performing fault

restarts.

Default: 10.0 s

Min.: 0.5

Max.: 600.0

167

L5-05

(0467)

Fault Reset Operation

Selection

Fault Reset Sel

0: Continuous

1: Use L5-04 Time

0: Continuously attempt to restart while incrementing restart

counter only at a successful restart (same as F7 and G7).

1: Attempt to restart with the interval time set in L5-04 and

increment the restart counter with each attempt (same as V7).

Default: 1

Range: 0, 1

167

u

L6: Torque Detection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

L6-01

(04A1)

Torque Detection

Selection 1

Torq Det 1 Sel

0: Disabled

1: OL Alm at SpdAgr

2: OL Alm dur RUN

3: OL Flt at SpdAgr

4: OL Flt dur RUN

5: UL Alm at SpdAgr

6: UL Alm dur RUN

7: UL Flt at SpdAgr

8: UL Flt dur RUN

9: UL6Alm at SpdAgr

10: UL6Alm dur RUN

11: UL6Flt at SpdAgr

12: UL6Flt dur RUN

0: Disabled

1: oL3 detection only active during speed agree, operation

continues after detection

2: oL3 detection always active during run, operation continues

after detection

3: oL3 detection only active during speed agree, output shuts

down on an oL3 fault

4: oL3 detection always active during run, output shuts down

on an oL3 fault

5: UL3 detection only active during speed agree, operation

continues after detection

6: UL3 detection always active during run, operation continues

after detection

7: UL3 detection only active during speed agree, output shuts

down on an oL3 fault

8: UL3 detection always active during run, output shuts down

on an oL3 fault

9: UL6 at speed agree (alarm)

10: UL6 at run (alarm)

11: UL6 at speed agree (fault)

12: UL6 at run (fault)

Default: 0

Range: 0 to 12

128

L6-02

(04A2)

Torque Detection Level

1

Torq Det 1 Lvl

Sets the overtorque and undertorque detection level.

Default: 15%

Min.: 0

Max.: 300

129

B.9 L: Protection Function

292

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual