S3: secondary pi (pi2) control – Yaskawa Z1000U User Manual
Page 302
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
S2-17
(3216)
Sequence Timer 4 Stop
Time
Tmr 4 Stop Time
Sets the stop time for timer 4. The value must be set greater than
or equal to S2-16.
Default: 00:00
Min.: 00:00
Max.: 24:00
–
S2-18
(3217)
Sequence Timer 4 Day
Selection
Tmr 4 Day Sel
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Sets the days for which sequence timer 4 is active.
0: Timer disabled
1: Daily
2: Mon - Fri
3: Sat - Sun
4: Monday
5: Tuesday
6: Wednesday
7: Thursday
8: Friday
9: Saturday
10: Sunday
Default: 0
Range: 0 to 10
–
S2-19
(3218)
Sequence Timer 4
Selection
Tmr 4 Seq Sel
0: Digital out only
1: Run
2: Run - PID Disable
Sets the action that occurs when sequence timer 4 is active.
0: Digital output only
1: Run
2: Run - PID disable
Default: 0
Range: 0 to 2
–
S2-20
(3219)
Sequence Timer 4
Reference Source
Tmr 4 Ref Source
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial com
6: Option PCB
Selects the frequency reference source used for running the drive
when sequence timer 4 is active (only applicable when S2-19 is
set to 1 or 2).
0: Operator (d1-01)
1: Operator (d1-02)
2: Operator (d1-03)
3: Operator (d1-04)
4: Terminals
5: Serial communication
6: Option card
Default: 0
Range: 0 to 6
–
u
S3: Secondary PI (PI2) Control
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
S3-01
(321A) Secondary PI Enable
Selection
PI2 Enable Sel
0: Disabled
1: Always
2: Drive running
3: Motor running
0: Secondary PI disabled
1: Always
2: Drive running
3: Motor running
Default: 0
Range: 0 to 3
–
S3-02
(321B) Secondary PI User
Display
PI2 UsrDspMaxVal
Sets the scale value of 100% PI input.
Default: 10000
Min.: 0
Max.: 60000
–
S3-03
(321C) Secondary PI Display
Digits
PI2 UsrDspDigits
0: No Dec (XXXXX)
1: 1 Dec (XXXX.X)
2. 2 Dec (XXX.XX)
3: 3 Dec (XX.XXX)
0: No decimal places
1: One decimal place
2: Two decimal places
3: Three decimal places
Default: 2
Range: 0 to 3
–
S3-04
(321D) Secondary PI Unit
Selection
PI2 Unit Sel
0: WC
1: PSI
2: GPM
3: °F
4: CFM
5: CMH
6: LPH
7: LPS
8: Bar
9: Pa
10: °C
11: Mtr
12: LPM
13: CMM
14: No unit
15: %
0: Inch of water (WC)
1: Pounds per square inch (PSI)
2: Gallons per minute (GPM)
3: Degrees Fahrenheit (F)
4: Cubic feet per minute (CFM)
5: Cubic meters per hour (CMH)
6: Liters per hour (LPH)
7: Liters per second (LPS)
8: Bar (Bar)
9: Pascals (Pa)
10: Degrees Celsius (C)
11: Meters (Mtr) (Ft: Feet)
12: Liters per minute (LPM)
13: Cubic meters per minute (CMM)
14: No unit
15: Percentage (%)
Default: 15
Range: 0 to 15
–
B.12 S: Special Application
302
YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual