Item

Specification

Environment

Area of Use

Indoors

Ambient Temperature

IP20/NEMA Type 1 enclosure: -10 °C to +40 °C (14 °F to 104 °F)

IP00 enclosure: -10 °C to +50 °C (14 °F to 122 °F)

Humidity

95 RH% or less (no condensation)

Storage Temperature

-20 °C to +60 °C (short-term temperature during transportation)

Altitude

Up to 1000 meters without derating, up to 3000 m with output current and voltage derating.

Vibration/Shock

10 to 20 Hz: 9.8 m/s

2

20 to 55 Hz: 5.9 m/s

2

(2o0028 to 2o0081 and 4o0011 to 4o0077)

2.0 m/s

2

(2o0104 to 2o0248 and 4o0096 to 4o0414)

Standard

• UL508C
• IEC/EN 61800-3, IEC/EN 61800-5-1

Protection Design

IP00/Open Type enclosure

<7>

, IP20/NEMA Type 1 enclosure

<1> Current derating is required. Select control modes in accordance with drive capacity.
<2> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different motors

and with changing motor temperature. Contact Yaskawa for consultation.

<3> Overload protection may be triggered when operating with 150% of the rated output current if the output frequency is less than 6 Hz.
<4> Actual specifications may vary depending on motor characteristics.
<5> A separate Momentary Power Loss Ride-Thru Unit is required if the application needs to continue running for up to 2 seconds during a momentary

power loss.

<6> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground

fault is present at the output.

<7> Attaching the top protective cover and bottom cover on an IP00 enclosure drive will convert the drive to a NEMA Type 1 drive.

A.2 Drive Specifications

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

247

A

Specifications