Fault reset methods, Reset the fault, 9 diagnosing and resetting faults – Yaskawa Z1000U User Manual

Page 219: Digital operator jvop-183

background image

Step

Display/Result

5.

Press

to view drive status information when fault occurred.

Parameter U2-58 helps determine the cause of a fault.

Parameters to be monitored differ depending on the control mode.

- MONITR -

U2-

03

= 60.00Hz

U2-04= 60.00Hz

U2-05= XX.XXA

DRV

Frequency Ref

Rdy

RSEQ

RREF

- MONITR -

U2-01= -----

U2-02= oC

DRV Rdy

RSEQ

RREF

U2-

58

= 60.00Hz

PowerSupply Freq

FWD

JOG

FWD

JOG

u

Fault Reset Methods

When a fault occurs, the cause of the fault must be removed and the drive must be restarted. The table below lists the different

ways to restart the drive.

After the Fault Occurs

Procedure

Fix the cause of the fault, restart the drive, and

reset the fault.

Press

on the HOA keypad when the error code

is displayed.

F2

F1

ESC

M

M

AUTO

OFF

ENTER

RESET

-DRIVE-

U1- 01=60.00Hz

----------------

U1- 02=60.00Hz

JOG FWD FWD/REV

-Rdy-

ALM

DIGITAL OPERATOR JVOP-183

HAND

Freq Ref (OPR)

Resetting via Fault Reset Digital Input S4

Close then open the fault signal digital input via

terminal S4. S4 is set for “Fault Reset” as default

(H1-04 = 14).

Fault Reset Switch

Drive

S4 Fault Reset Digital Input

SC Digital Input Common

Turn off the main power supply if the above methods do not reset the fault. Reapply power after the

HOA keypad display has turned off.

ON

OFF

2

1

Note:

If the Run command is present, the drive will disregard any attempts to reset the fault. Remove the Run command before attempting to clear

a fault situation.

5.9 Diagnosing and Resetting Faults

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

219

5

Troubleshooting