Flowchart A: Basic Start-Up and Motor Tuning
Flowchart A in
describes a basic start-up sequence that varies slightly depending on the application. Use the drive
default parameter settings in simple applications that do not require high precision.
YES
NO
START
Install and wire the drive.
Apply main power on to the drive
Adhere to safety messages concerning application of power
Application Presets
A1-06 used ?
Set the control mode in parameter A1-02.
Refer to
Application
Selection section
Set the basic parameters
b1-01/02 for frequency reference and run command source selection
H1-oo, H2-oo, H3-oo, H4-oo for I/O terminal setting
d1-oo for multi-speed references if used
C1-oo and C2-oo for accel./decel. and S-curve time settings
Fine tune parameters. Adjust application settings (PID, ...) if necessary.
Check the machine operation and verify parameter settings.
Drive is ready to run the application.
E1-01 for input voltage setting
Figure 4.9 Basic Start-Up