A.4 Drive Derating Data

The drive can be operated at above the rated temperature, altitude, and default carrier frequency by derating the drive capacity.

u

Rated Current Depending on Carrier Frequency

The table below shows the drive output current depending on the carrier frequency settings.
Use the data in the following tables to linearly calculate output current values for carrier frequencies not listed.

Table A.7 Three-Phase 200 V Class Carrier Frequency and Current Derating

Three-Phase 200 V Class

Drive Model

Rated Current [A]

4 kHz

6 kHz

8 kHz

10 kHz

2o0028

28

25

22

20

2o0042

42

38

34

29

2o0054

54

49

43

38

2o0068

68

61

54

48

2o0081

81

73

65

57

2o0104

104

94

83

2o0130

130

117

104

2o0154

154

139

2o0192

192

173

2o0248

248

Table A.8 Three-Phase 400 V Class Carrier Frequency and Current Derating

Three-Phase 400 V Class

Drive Model

Rated Current [A]

4 kHz

6 kHz

8 kHz

10 kHz

4o0011

11

9.9

8.8

7.7

4o0014

14

13

11

9.8

4o0021

21

19

17

15

4o0027

27

24

22

19

4o0034

34

31

27

24

4o0040

40

36

32

28

4o0052

52

47

42

36

4o0065

65

59

52

46

4o0077

77

69

62

54

4o0096

96

86

77

4o0124

124

112

99

4o0156

156

140

4o0180

180

162

4o0216

216

4o0240

240

4o0302

302

4o0361

361

4o0414

414

A.4 Drive Derating Data