No.

Name

Setting Range

Default

b5-35

PID Input Limit

0.0 to 1000.0%

1000.0%

n

b5-36: PID Feedback High Detection Level

Sets the feedback level used for PID feedback high detection. The PID feedback must exceed this level for longer than the

time set to b5-37 before feedback loss is detected.

No.

Name

Setting Range

Default

b5-36

PID Feedback High Detection Level

0 to 100%

100%

n

b5-37: PID Feedback High Detection Time

Sets the time that the PID feedback must exceed the value set to b5-36 before feedback loss is detected.

No.

Name

Setting Range

Default

b5-37

PID Feedback High Detection Time

0.0 to 25.5 s

1.0 s

n

b5-38, b5-39: PID Setpoint User Display, PID Setpoint Display Digits

When parameter b5-20 is set to 3, parameters b5-38 and b5-39 set a user-defined display for the PID setpoint (b5-19) and PID

feedback monitors (U5-01, U5-04).
Parameter b5-38 determines the display value when the maximum frequency is output and parameter b5-39 determines the

number of digits. The setting value is equal to the number of decimal places.

No.

Name

Setting Range

Default

b5-38

PID Setpoint User Display

1 to 60000

Determined by

b5-20

b5-39

PID Setpoint Display Digits

0 to 3

Determined by

b5-20

Setting 0: No Decimal Places
Setting 1: One Decimal Place
Setting 2: Two Decimal Places
Setting 3: Three Decimal Places

n

b5-40: Frequency Reference Monitor Content During PID

Sets the content of the frequency reference monitor display (U1-01) when PID control is active.

No.

Name

Setting Range

Default

b5-40

Frequency Reference Monitor Content During PID

0, 1

0

Setting 0: Frequency Reference after PID

Monitor U1-01 displays the frequency reference increased or reduced for the PID output.

Setting 1: Frequency Reference

Monitor U1-01 displays the frequency reference value.

n

b5-41: PID Unit Selection

Sets the display units in U5-14 and U5-15.

No.

Name

Setting Range

Default

b5-41

PID Unit Selection

0 to 14

0

4.12 Advanced Drive Setup Adjustments

154