beautypg.com

C6: carrier frequency, C7: voltage adjustment – Yaskawa Z1000U User Manual

Page 264

background image

u

C6: Carrier Frequency

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C6-02

(0224)

Carrier Frequency

Selection

CarrierFreq Sel

1: Fc=4.0 kHz

2: Fc=6.0 kHz

3: Fc=8.0 kHz

4: Fc=10.0 kHz

F: Program

1: 4.0 kHz

2: 6.0 kHz

3: 8.0 kHz

4: 10.0 kHz

F: User-defined (determined by C6-03 through C6-05)

Default:

<1>

Range: 1 to 4; F

120

C6-03

(0225)

Carrier Frequency

Upper Limit

CarrierFreq Max

Determines the upper and lower limits for the carrier frequency.

Carrier Frequency

E1-04

Max Output

Frequency

Output Frequency

× (C6-05) × K

Output

Frequency

C6-03

C6-04

Default:

<2>

Min.: 4.0 kHz

Max.: 10.0 kHz

157

C6-04

(0226)

Carrier Frequency

Lower Limit

CarrierFreq Min

Default:

<2>

Min.: 4.0 kHz

Max.: 10.0 kHz

157

C6-05

(0227)

Carrier Frequency

Proportional Gain

CarrierFreq Gain

Default:

<2>

Min.: 0

Max.: 99

157

C6-09

(022B)

Carrier Frequency

during Rotational Auto-

Tuning

Carrier in tune

0: Fc = 5kHz

1: Fc = C6-03

OLV/PM

OLV/PM

0: Carrier Frequency = 4 kHz. In PM control modes, this value

is 2 kHz.

1: Setting value for C6-03. In PM control modes, this value is

the carrier frequency set in C6-02.

Default: 0

Range: 0, 1

<1> Default setting value is dependent on parameters A1-02, Control Method Selection and o2-04, Drive Model Selection.
<2> Default setting value is dependent on parameter C6-02, Carrier Frequency Selection.

u

C7: Voltage Adjustment

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C7-43

(112A)

Input Voltage Offset

Adjustment

InputVolt Offset

Adjusts the offset for the input voltage circuit when the control

board is replaced.

0000: Standard

0002: Offset adjustment not required

Default: 0000

Range: 0000 to

9999

C7-56

(1107)

Power Factor Control

Selection

PF Control Sel

0: PF Ctrl Disabled

1: PF Ctrl Enabled

0: Power factor control disabled

1: Power factor control enabled

Default: 0

Range: 0, 1

C7-60

(0B1C)

Output Voltage Limit

Mode Selection

V Out Limit Sel

0: Limit Harmonics

1: Improve PF

0: Harmonic suppression priority mode

1: High output voltage mode

Default: 1

Range: 0, 1

B.4 C: Tuning

264

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual