12 advanced drive setup adjustments, Setting specification characteristic application f, Table 4.29 high starting torque, settings 8 to b – Yaskawa Z1000U User Manual
Page 160: Table 4.30 rated output operation, settings c to f

Setting
Specification
Characteristic
Application
F
<1>
60 Hz
Constant torque
For general purpose applications. Torque remains constant
regardless of changes to speed.
<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04
to E1-13 are the same as those of setting 1.
The following tables show details on predefined V/f patterns.
Predefined V/f Patterns for Models 4o0011 and 4o0014
Table 4.27 Constant Torque Characteristics, Settings 0 to 3
Setting = 0
50 Hz
Setting = 1
60 Hz
Setting = 2
60 Hz
Setting = 3
72 Hz
0
18
400
1.3 2.5
50
30
V
oltage (V)
Frequency (Hz)
0
18
30
400
1.5 3
60
V
oltage (V)
Frequency (Hz)
0
18
30
400
1.5 3
60
50
V
oltage (V)
Frequency (Hz)
0
18
30
400
1.5 3
72
60
V
oltage (V)
Frequency (Hz)
Table 4.28 Derated Torque Characteristics, Settings 4 to 7
Setting = 4
50 Hz
Setting = 5
50 Hz
Setting = 6
60 Hz
Setting = 7
60 Hz
0
16
400
1.3
25
50
70
V
oltage (V)
Frequency (Hz)
0
18
400
1.3
25
50
100
V
oltage (V)
Frequency (Hz)
0
16
400
1.5
30
60
70
V
oltage (V)
Frequency (Hz)
0
18
400
1.5
30
60
100
V
oltage (V)
Frequency (Hz)
Table 4.29 High Starting Torque, Settings 8 to B
Setting = 8
50 Hz
Setting = 9
50 Hz
Setting = A
60 Hz
Setting = B
60 Hz
0
22
400
1.3 2.5
50
38
V
oltage (V)
Frequency (Hz)
0
26
400
1.3 2.5
50
48
V
oltage (V)
Frequency (Hz)
0
22
400
1.5 3
60
38
V
oltage (V)
Frequency (Hz)
0
30
400
1.5 3
60
48
V
oltage (V)
Frequency (Hz)
Table 4.30 Rated Output Operation, Settings C to F
Setting = C
90 Hz
Setting = D
120 Hz
Setting = E
180 Hz
Setting = F
60 Hz
0
18
30
400
1.5 3
90
60
V
oltage (V)
Frequency (Hz)
0
18
30
400
1.5 3
120
60
V
oltage (V)
Frequency (Hz)
0
18
30
400
1.5 3
180
60
V
oltage (V)
Frequency (Hz)
0
18
30
400
1.5 3
60
V
oltage (V)
Frequency (Hz)
Predefined V/f Patterns for Models 2o0028 to 2o0192 and 4o0021 to 4o0124
The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives.
Table 4.31 Rated Torque Characteristics, Settings 0 to 3
Setting = 0
50 Hz
Setting = 1
60 Hz
Setting = 2
60 Hz
Setting = 3
72 Hz
0
7
200
1.3 2.5
50
14
V
oltage (V)
Frequency (Hz)
0
7
14
200
1.5 3
60
V
oltage (V)
Frequency (Hz)
V
oltage (V)
Frequency (Hz)
0
7
14
200
1.5 3
60
50
0
7
14
200
1.5 3
72
60
V
oltage (V)
Frequency (Hz)
4.12 Advanced Drive Setup Adjustments
160
YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual