beautypg.com

Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual

Page 91

background image

Publication AG-UM008C-EN-P - February 2005

Configuring MicroLogix 1100/1200/1500 Controllers 3-23

Use Worksheet 3.3 MicroLogix 1100/1200/1500 DF1 Half-Duplex Slave
Station Configuration
(pageD-11) for an example configuration and to
record your station’s configuration.

Define these parameters when configuring a MicroLogix
1100/1200/1500 controller as a slave station.

2. On the Channel tab, choose

DF1 Half-Duplex Slave for
your Driver.

3. Configure the communication

driver characteristics
according to Table 3.5.

Table 3.5 Configuring a MicroLogix 1100/1200/1500 controller as a Slave Station

Parameter

Selections

Baud Rate

Select a communication rate that all devices in your system support. Configure all
devices in the system for the same communication rate.

Parity

Parity provides additional message packet error detection. To implement even parity
checking, choose Even. To implement no parity checking, choose None.

Node Address

A node address identifies the controller on the DF1 half-duplex link. Each station on a
link must have a unique node address. Choose an address between 0

10

and 254

10.

Node

address 255

10

is the broadcast address, which you cannot select as a station’s

individual address.

Control Line

This parameter defines the mode in which the driver operates. Choose a method
appropriate for your system’s configuration:

If you are not using a modem, choose NO HANDSHAKING.

If the master modem is full duplex and the slave modem is half-duplex, choose
HALF-DUPLEX MODEM (RTS/CTS Handshaking).

See page 3-8 for descriptions of the control line operation settings.

Error Detection

With this selection, you choose how the controller checks the accuracy of each DF1
packet transmission.
BCC: This algorithm provides a medium level of data security. It cannot detect:

transposition of bytes during transmission of a packet

the insertion or deletion of data values of zero within a packet

CRC: This algorithm provides a higher level of data security.
Select an error detection method that all devices in your configuration can use.
When possible, choose CRC.