Publication AG-UM008C-EN-P - February 2005
7-38 Configuring Logix Controllers
Logix Controller Error
Codes for PLC and SLC
Messages
With the release Logix R10.x firmware, you will find new error code
values for errors that are associated with PLC and SLC message types
(PCCC messages).
•
This change lets RSLogix 5000 software display a more
meaningful description for many of the errors. Previously the
software did not give a description for any of the errors
associated with the 00F0 error code.
•
The change also makes the error codes more consistent with
errors returned by other controllers, such as PLC-5 controllers.
The following table shows the change in the error code values from
R9.x and earlier to R10.x and later. As a result of the change, the .ERR
member returns a unique value for each PCCC error. The .EXERR is no
longer required for these errors.
R9.x and earlier
R10.x and later
Description
.ERR
.EXERR
.ERR
.EXERR
0010
1000
Illegal command or format from local processor
0020
2000
Communication module not working
0030
3000
Remote node is missing, disconnected, or shut down
0040
4000
Processor connected but faulted (hardware)
0050
5000
Wrong station number
0060
6000
Requested function is not available
0070
7000
Processor is in Program mode
0080
8000
Processor’s compatibility file does not exist
0090
9000
Remote node cannot buffer command
00B0
B000
Processor is downloading so it is not accessible
00F0
0001
F001
Processor incorrectly converted the address
00F0
0002
F002
Incomplete address
00F0
0003
F003
Incorrect address
00F0
0004
F004
Illegal address format - symbol not found
00F0
0005
F005
Illegal address format - symbol has 0 or greater than the maximum number of
characters supported by the device
00F0
0006
F006
Address file does not exist in target processor
00F0
0007
F007
Destination file is too small for the number of words requested
00F0
0008
F008
Cannot complete request
Situation changed during multipacket operation
00F0
0009
F009
Data or file is too large
Memory unavailable
00F0
000A
F00A
Target processor cannot put requested information in packets
00F0
000B
F00B
Privilege error; access denied