8-6 Configuring Modems

encased in a rugged steel enclosure with large mounting flanges for
ease of installation.

The DLM4300 connects to the PC/PLC through a DB-9 female
connector. All connections and LEDs are located at the front of the
modem. Line connection is made through the RJ-45 jack, as are the
LEDs for Data Out, Data In, Carrier Detected and Power, providing
visible confirmation of modem operation and diagnosis.

Figure 8.3 DLM4300 Assignments

LLM1000-2 and LLM1000-4

The LLM1000 series modems are 2 and 4 wire Frequency-shift keyed,
half-duplex/simplex, Bell 202/CCITT V.23 compatible, 0 to 1200 baud
modem that interface with Allen-Bradley equipment. They are
designed to be used on private, leased unswitched telephone lines or
any dedicated two conductor wire (twisted or untwisted, shielded or

Table 8.3 DLM4300 DB-9 Assignments

DLM4300 Pin #

PLC-5 25-Pin

AIC+, Logix5550, PC, or
SLC 500 9-Pin

Assignment

1

8

1

Carrier Detect

2

3

2

Transmit Data

3

2

3

Receive Data

4

20

4

DTR

5

7

5

Signal Ground

6

6

6

DSR

7

4

7

RTS

8

5

8

CTS

9

NC

NC

Ground

6

7

8

9

1

2

3

4

5