3-68 Configuring MicroLogix 1100/1200/1500 Controllers

Information for Creating Your Own Application

Controller Receives Communications Packet

Table 3.14 Command Structure

DST

SRC

CMD 0f

STS

TNS

FNC A2

Byte Size

File No.

File Tpe

Ele. No.

S/Ele. No.

Field

Function

Description

DST

Destination Node

SRC

Source Node

CMD

Command Code

STS

Status Code

Set to zero (0)

TNS

Transaction Number

Always 2 bytes

FNC

Function Code

Byte Size

Number of bytes to be read

Formatted string length (see equation below)

File Number

Always set to zero (0)

File Type

Must be A5 (hex)

Element Number

Queue number

Determines the queue to be read (0 to 255)

Sub/Element Number

Always set to zero (0)

Table 3.15 Equation

Record Field 1 + Record Field 2 + Record Field 3 … + Record Field 7

= Formatted

String Length

Table 3.16 Record Field Sizes

Data Type

Maximum Size

Word

7 bytes (characters)

Long Word

12 bytes (characters)

Date Field

11 bytes (characters)

Time Field

9 bytes (characters)

TIP

The formatted string length cannot exceed 80 bytes
in length.

TIP

The last byte will be a zero value representing the
terminator character.