beautypg.com

Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual

Page 182

background image

Publication AG-UM008C-EN-P - February 2005

4-44 Configuring SLC 5/03, 5/04, and 5/05 Processors

This MSG example tells the SLC 5/03, 5/04, or 5/05 master station to
write the information from its S:37 through its serial port (channel 0)
to the PLC-5 slave station 11

10

. The data’s destination is N19:0 of the

PLC-5 slave station. For a Logix slave station, a tag name would have
to already have been mapped to N19. Alternatively, SLC 5/03 (OS 302
C or higher), 5/04 (OS 401 C or higher) and 5/05 processors support
logical ASCII addressing, which means any Logix controller tag can be
written to by entering the tag name in double quotes in the Target’s
Data Table Address field.

Figure 4.7 Read MSG from an SLC 5/03, 5/04, or 5/05 Processor to a PLC-5 Processor
or Logix Controller.

MSG being sent to a
PLC-5 processor or a
Logix controller