Configuring the processor as a station on a – Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual

Page 58

background image

Publication AG-UM008C-EN-P - February 2005

2-20 Configuring Enhanced PLC-5 Processors

Configuring the Processor
as a Station on a
Point-to-Point Link

To configure the processor as a station on a point-to-point link, place
the processor in program mode and follow the steps below using your
programming software:

Use Table 2.6. to help you understand the screen parameters you
need to specify on the Channel Configuration screen.

Use Worksheet 2.4 (page D-8) for an example configuration and to
record your station’s configuration.

1. Double-click on the Channel

Configuration file to bring up
the Edit Channel Properties
interface.

2. On the Channel 0 tab, choose

System (Point-to-Point) for
your Communication Mode.

3. Configure the Serial Port

parameters according to

Table 2.6.

4. Configure the Options

parameters according to

Table 2.6.

5. When all parameters are set,

click OK.