Data-linc group, Data-linc group -23, Srm6000/6100/6200e -23 – Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual
Page 289
![background image](/manuals/580293/289/background.png)
Publication AG-UM008C-EN-P - February 2005
Configuring Modems 8-23
DATA-LINC Group
Use the following table to determine which DATA-LINC radio modem
you need. Refer to
for cabling information
. Consult
DATA-LINC for specific information regarding the installation of
DATA-LINC products.
SRM6000/6100/6200E
The DATA-LINC SRM6000, SRM6100 and SRM6200E are license-free
spread spectrum frequency hopping wireless modems that can
interface with Allen-Bradley PLCs. The modems can be configured as
master, remote, or repeater (SRM6000/6100 only) and data
communications are asynchronous. Baud rates can be set as high as
115.2K.
Table 8.21 DATA-LINC Radio Modem
Spread-spectrum
Frequency
Topology
A-B Protocol
Maximum
Distance
Line-of-Sight
DATA-LINC
Model #
902-928 MHz
Point-to-Point
DF1 Full-duplex
20 miles
SRM 6000
Point-to-Multipoint
DF1 Half-duplex
SRM 6000-SLC
(2)
SRM 6000-PLC
(3)
2400-2484 MHz
Point-to-Point
DF1 Full-duplex
7 miles
SRM 6100
Point-to-Multipoint
DF1 Half-duplex
SRM 6100-SLC
SRM 6100-PLC
902-928 MHz
Point-to-Point
Ethernet
(1)
15 miles
SRM 6200E
Point-to-Multipoint
SRM 6200E-SLC
SRM 6200E-PLC
(1) 10BASE-T connector
(2) 1746 chassis mount
(3) 1771 rack mount
TIP
For additional modem specifications consult your
DATA-LINC user documentation or
www.data-linc.com