Chapter objectives, Overview, Chapter 5 – Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual
Page 187: Chapter objectives -1 overview -1, Chapter

1
Publication AG-UM008C-EN-P - February 2005
Chapter
5
Configuring SLC 500 Processors with 1747-KE
Interface Modules
Chapter Objectives
This chapter helps you set up an SLC 500 fixed or modular processor
(SLC 5/01 or 5/02 processor) with a 1747-KE as a remote station or as
a station on a point-to-point link.
Overview
To configure an SLC 500 processor with a 1747-KE interface module
as a remote station:
1. Install the processor (modular processors only).
2. Install the 1747-KE module.
3. Configure the processor using your programming software.
4. Define the 1747-KE communication characteristics using an
ASCII terminal or terminal emulation software like
Hyperterminal in Windows 95. Connect a properly wired cable
to the interface module’s serial port (DF1 port).
5. Install and configure the modem for communication with the
1747-KE module; connect the modem to the 1747-KE module’s
serial channel. See Chapter 8.
For information about:
See page:
an overview of the tasks required to configure an SLC 500 processor
with a 1747-KE module as a remote station
installing the SLC 500 processor
installing the 1747-KE interface module
configuring the SLC 500 processor
configuring the 1747-KE interface module
configuring messages in the SLC 5/02 processor