7-24 Configuring Logix Controllers
DF1 Point-to-Point
Diagnostic Counters
DF1 Point-to-Point driver status data is stored in the Diagnostic
Counter attribute of the DF1 communication object. You must define a
controller tag to be the destination for this data and copy the system
data to this tag using a GSV instruction. For the required ladder logic,
see page 7-25.
1. To bring up the Controller Tag
interface, click on the Controller Tags
icon.
2. For details of the
DisgnosticCounter
files, see Table 7.9.
Table 7.9 DF1 Full-Duplex (Point-to-Point) Diagnostic Counters
Status Field
Diagnostic Tag Array
Location
Definition
signature (67
10
)
word 0
DF1 Point-to-Point is the configured protocol
DTR (Data Terminal Ready)
word 1;bit 4
The status of the DTR handshaking line (asserted by the controller)
DCD (Data Carrier Detect)
word 1;bit 3
The status of the DCD handshaking line (received by the controller)
DSR (Data Set Ready)
word 1;bit 2
The status of the DSR handshaking line (received by the controller)
RTS (Request to Send)
word 1;bit 1
The status of the RTS handshaking line (asserted by the controller)
CTS (Clear to Send)
word 1;bit 0
The status of the CTS handshaking line (received by the controller)
packets sent
word 2
The total number of DF1 packets sent by the controller (including
message retries)
packets received
word 3
The number of packets received with no errors
undelivered packets
word 4
The number of packets that were sent by the controller but not
acknowledged by the destination device
unused
word 5