3-60 Configuring MicroLogix 1100/1200/1500 Controllers

Number of Records

Using Queue 0 as an example, each record consumes:

In this example, each record consumes 18 bytes. So if one queue was
configured, the maximum number of records that could be stored
would be 2730. The maximum number of records is calculated by:

Maximum Number of Records = Data Log File Size/Record Size

= 48K bytes/18 bytes

= (48)(1024)/18

= 2730 records

Example Queue 5

Record Field

Memory Consumption

Date

2 bytes

Time

2 bytes

N7:11

2 bytes

L14:0

4 bytes

T4:5.ACC

2 bytes

I1:3.0

2 bytes

B3:2

2 bytes

Integrity Check

2 bytes

Total

18 bytes

Table 3.12 Queue 5 (Time = , Delimiter = TAB)

Time

N7:11

I1:3.0

I1:2.1

Record 0

20:00:00

TAB

2315

TAB

8190

TAB

4465

Record 1

20:30:00

TAB

2400

TAB

8210

TAB

4375

Record 2

21:00:00

TAB

2275

TAB

8150

TAB

4335

Record 3

21:30:00

TAB

2380

TAB

8195

TAB

4360

Record 4

22:00:00

TAB

2293

TAB

8390

TAB

4375

Record 5

22:30:00

TAB

2301

TAB

8400

TAB

4405

Record 6

23:00:00

TAB

2308

TAB

8100

TAB

4395