beautypg.com

Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual

Page 281

background image

Publication AG-UM008C-EN-P - February 2005

Configuring Modems 8-15

Cable Pin Assignments

The Model 137-001 requires a 15-pin male connector with the pin
assignments shown below or these MARC cable assemblies:

127-056 (1785-KE to MARC 137-001)

127-067 (1785 PLC-5/xx to MARC 137-001)

Figure 8.9 MARC, Inc. Model 137-001

Table 8.12 MARC, Inc. Model 137-001 Pin Assignments

Switch Settings

For Bell 202 full-duplex operating mode, set the switches on Model
137-001 according to those in Table 8.13. For Bell 202 half-duplex
mode (point-to-multipoint), set the switches on Model 166-101
according to those in Table 8.14.

MARC

15-pin D female
port

RJ11 jack
5 Receive(-)
4 Transmit (-)
3 Transmit (+)
2 Receive (+)

To Allen-Bradley PLC-5/xx
or 1785-KE

Modem

15-pin female

Pin Name

Pin Name

PLC-5

25-pin female

1785-KE

15-pin female

1

DCD.OUT

DCD.IN

8

8

2

TXD.IN

TXD.OUT

2

2

3

RXD.OUT

RXD.IN

3

3

4

DTR.IN

DTR.OUT

20

(2)

(2) Pin 6 is jumpered (within the connector) to pin 20.

11

(3)

(3) Pin 6 is jumpered (within the connector) to pin 11.

5

(1)

(1) Pin 5 is jumpered (within the connector) to pin 9.

SIG.GND

SIG.GND

7

7

(4)

(4) Pin 7 is jumpered (within the connector) to pin 13.

7

RTS.IN

RTS.OUT

4

4

8

CTS.OUT

CTS.IN

5

5