beautypg.com

Figure 6.5 – Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual

Page 223

background image

Publication AG-UM008C-EN-P - February 2005

Configuring MicroLogix 1000 Controllers 6-19

Figure 6.5 Write MSG Instruction from a MicroLogix 1000 Controller to a PLC-5
Processor

This MSG example is telling the MicroLogix 1000 station (station 99

10

)

to write the information from its N7:10-N7:15 to the PLC-5 station 31

10.

The data’s destination is N99:10 (for a target byte offset of 20

10

) of the

PLC-5 processor.

For example, if the MicroLogix 1000 controller in this example is
station 99

10

, then it writes the data from its N7:10 - N:15 into N99 of

the PLC-5 station. File N99 must exist in the PLC-5 in order for it to
receive data from the MicroLogix 1000 station.

ladder rung

setup screen

IMPORTANT

The MicroLogix 1000 controller writes the
information into an integer file in the PLC-5
processor’s data table. The integer file number is
equal to the MicroLogix 1000 controller’s station
address (this event is called PLC-2 emulation).