beautypg.com

Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual

Page 299

background image

Publication AG-UM008C-EN-P - February 2005

Configuring Modems 8-33

1785-KE

1747-KE
1746-BAS
KF2 or KF3 module
PC
SLC 5/03, 5/04, or 5/05
Logix5550
or AIC+ for

MicroLogix 1000

If you are connecting
to an Allen-Bradley

Use these pin assignments for cable interface from the ESTeem modem to the A-B module

Modem

25-pin female

(1)

(1) A-B 1770-CP cable (16.5’)

Pin Name

Pin Name

1785-KE

15-pin female

NC

Shield

Shield

1

2

TXD.IN

TXD.OUT

2

3

RXD.OUT

RXD.IN

3

4

RTS.IN

RTS.OUT

4

5

CTS.OUT

CTS.IN

5

6

DSR.OUT

DSR.IN

6

7

SIG.GND

Signal

7

11

SIG.GND

Ground

13

8

DCD.OUT

DCD.IN

8

20

DTR.IN

DTR.OUT

11

22

RING

RING

9

Modem

25-pin female

(1)

(1) ESTeem cable # AA07 (6’) for KF2, KF3. ESTeem cable #AA061 (6’) for all others.

Pin Name

Pin Name

KF2, KF3 module

25-pin male

PC, SLC, Logix5550
and AIC+

9-pin male

2

TXD.IN

TXD.OUT

2

3

3

RXD.OUT

RXD.IN

3

2

4

RTS.IN

RTS.OUT

4

7

5

CTS.OUT

CTS.IN

5

8

6

DSR.OUT

DSR.IN

6

6

7

SIG.GND

SIG.GND

7

5

8

DCD.IN

DCD.OUT

8

1

1

Shield