beautypg.com

Processor-to-processor -24, Processor-to-processor – Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual

Page 62

background image

Publication AG-UM008C-EN-P - February 2005

2-24 Configuring Enhanced PLC-5 Processors

Processor-to-Processor

A processor-to-processor message can be two types:

In a point-to-multipoint configuration, the messaging would be
between slave stations; the master station automatically routes
the message.

In a point-to-point configuration, the messaging would be
between the two connected peer devices.

The configuration of the network (point-to-multipoint vs.
point-to-point) and the configuration of the station (master, slave, or
peer) does not affect how you configure a MSG instruction. That is, a
MSG instruction being sent between two PLC-5 slave stations is
configured the same as a MSG instruction between two PLC-5
processors connected point-to-point, which is configured the same as
a MSG instruction between a PLC-5 master station and a PLC-5 slave
station. See Figure 2.5 through Figure 2.8 for example MSG control
blocks.

MSG from Slave
Station 1 to Slave
Station 2

Slave
Station 2

Master
Station

Slave
Station 1

Modem

Modem

Modem

Master Station
routes MSG to
Slave Station 2

Modem

Modem

Station 1

Station 2

MSG