Figure 5.7 – Rockwell Automation DAG6.5.8 APPLICATION GUIDE SCADA SYSTEM User Manual

Page 200

background image

Publication AG-UM008C-EN-P - February 2005

5-14 Configuring SLC 500 Processors with 1747-KE Interface Modules

Figure 5.7 Write MSG instruction from an SLC 5/02 processor to a PLC-5 processor.

This MSG example is telling the SLC 5/02 remote station (station 99

10

)

to write the information from its S:1 to S:6 to the PLC-5 master station
9

10

through the KE module 31

10.

The data’s destination is N99:10 (for

a target byte offset of 20

10

) of the PLC-5 processor.

For example, if the SLC 5/02 processor in this example is station 99

10

,

then it writes the data from its S:1 to S:6 into N99 of the PLC-5 master
station. File N99 must exist in the PLC-5 in order for it to receive data
from the SLC 5/02 remote station.

ladder rung

setup screen

IMPORTANT

The SLC 5/02 processor writes the information into
an integer file in the PLC-5 processor’s data table.
The integer file number is equal to the SLC 5/02
processor’s station address. (This event is called
PLC-2 emulation.)