Publication AG-UM008C-EN-P - February 2005

Basic DF1 Protocol Troubleshooting B-5

Table B.2 Identify the DF1 Half-Duplex Packets

See ANSI X3.4, CCITT V.3, or ISO 646 for the standard definition of
these characters.

Symbol

Hexadecimal

Binary

Type

Meaning

DLE SOH

10 01

0001 0000

0000 0001

control symbol

Start of header
Sender symbol that indicates the start of a
master station’s message

DLE STX

10 02

0001 0000

0000 0010

control symbol

Start of text
Sender symbol that separates the multi-drop
header from the data

DLE ETX BCC/CRC

10 03 xx(xx)

0001 0000

0000 0011

control symbol

End of text and checksum
Sender symbol that terminates a message

DLE EOT

10 04

0001 0000

0000 0100

control symbol

End of transmission
Response symbol used by remote stations as a
response to a poll when they have no
messages to send

DLE ENQ STN
BCC

10 05 xx xx

0001 0000

0000 0101

control symbol

Enquiry poll packet
Sender symbol, issued only by the master
station, that starts a poll command

DLE ACK

10 06

0001 0000

0000 0110

control symbol

Acknowledgment
Response symbol which signals that a
message has been successfully received

DLE DLE

10 10

0001 0000

0001 0000

data symbol

Represents the data value or STN value of 10
(hex)

DLE NAK

10 15

0001 0000

0001 0101

control symbol

Global link reset command only issued by the
master station during powerup or a serial port
reconfiguration
The command causes the remote station to
cancel all messages that are ready to transmit
to the master station. Typically, the remote
station returns an error code to the affected
MSG instructions.

STN

application specific

data symbol

Station number of the remote station on your
half-duplex link (00-FE)

APP DATA

application specific

data symbol

Single characters having values 00-0F and
11-FF
Includes data from application layer including
user programs and common application
routines