beautypg.com

Campbell Scientific LoggerNet Datalogger Support Software User Manual

Page 66

background image

Section 4. Setting up Datalogger Networks

Standard
Communications Enabled – Before communication can take place, all

devices in the chain must be enabled. When this box is selected, the Internet

protocol serial port is enabled for communication.

TAPI Line – Select the modem you want to use for communication. The

modems listed are defined by Windows as part of the computer’s Modem

Setup. All of the parameters for the modem, including the baud rate have to be

set using the Windows Modem Setup dialog. If you are using the same modem

for dialup access you may have to change the settings for the different

applications.

Advanced
Call-back Enabled – Enabling call-back tells LoggerNet to watch for a call-

back from the datalogger on this port. If there is a phone modem attached it

will be set to monitor for incoming calls.

Dataloggers depicted in the Setup Screen must be configured for call-back as

well. For mixed array dataloggers, set the Call-Back ID to some value other

than 0 to accomplish this. For CRBasic dataloggers, enable the Call-Back

Enabled check box for those dataloggers which should be enabled for call-

back.

Extra Response Time – In this field, specify the additional time that

LoggerNet should delay before terminating the communications link if there is

no response from the IPPort. Additional time may be needed in instances

where the communications link is noisy or network traffic is heavy.

Delay Hangup – The amount of time, in seconds and milliseconds, that

LoggerNet should delay before hanging up the link to the device. If a new

command to the device is issued before the delay has expired, communication

will not be terminated.

To communicate with dataloggers using the TAPI modem you

have to set the baud rate to match the communication capability

of the devices in the link. If you are using COM200 modems, the

baud rate must be set to 9600 on the TAPI modem. For use over

cell phone modems 1200 or 4800 baud may be required.

LoggerNet waits a certain amount of time for a response from each

device in a communications path. The extra response times

defined for the communications link are cumulative. Therefore,

the amount of time spent waiting for a device to respond is the

sum of all Extra Response Times defined, plus the default

response time for each device in the link. Add the minimum time

necessary since very long response times can delay other

scheduled events while waiting for a device that is not responding.

NOTES

4-10