beautypg.com

20 pakbustcpserver, Pakbustcpserver -44 – Campbell Scientific LoggerNet Datalogger Support Software User Manual

Page 100

background image

Section 4. Setting up Datalogger Networks

Advanced
Extra Response Time – The amount of additional time, in seconds, that

LoggerNet should wait for this device to respond. Note that Extra Response

Time is cumulative for all devices in the network.

PakBus Address – This field is for display only. It shows the PakBus address

that has been set up for the PakBus Port. This address can be changed by going

to the Setup Screen’s Options | LoggerNet PakBus Settings menu item.

4.2.4.20 PakBusTcpServer

The PakBus TcpServer can accommodate multiple incoming PakBus/TCP

connections to service the stations attached to it. Therefore, the same IP port

can be used to listen for incoming connections from multiple dataloggers.

The Outbound PakBus Connections portion of the Routing tab can be used to

specify IP addresses and port numbers to be used for outgoing connections to

specific dataloggers attached to the PakBus TcpServer. The Maintained Nodes

portion of the Routing tab can be used to cause LoggerNet to maintain a

connection with a range of these dataloggers, once an incoming connection has

been established.

Hardware Tab, Standard
Communications Enabled – This check box is used to turn communication on

or off. This check box must be enabled for any communication to take place

over the PakBus TcpServer.

PakBus Port Always Open – By default, a port is only active when

communication is taking place with a device. Selecting this option will keep

the port always open for each datalogger attached to the PakBus TcpServer.

Maximum Time On-Line – This field is used to define a time limit for

maintaining a connection to the device. (This may be useful in avoiding costly

communication costs, in the event that a connection to a station is inadvertently

maintained for a long period of time.) Maximum Time On-Line applies to both

scheduled connections and manual connections. However, for manual

connections from the Connect Screen, it is always best to manually disconnect

rather than relying on LoggerNet to disconnect for you.

When the device is contacted on a schedule, communication with the device

will be terminated once this time limit is exceeded. A value of 0 in this field

indicates that there is no time limit on maintaining a connection to the device.

When the device is connected in the Connect Screen and the time limit

approaches, a dialog box is displayed warning the user that Max Time On-Line

is about to be exceeded. The dialog box has

Reset Max Time and Don’t Reset

buttons. If the

Reset Max Time button is pressed, the Max Time On-Line

counter will be reset. If the

Don’t Reset button is pressed or if no button is

pressed, the connection will be terminated when Max Time On-Line is

reached.

The format for this field is 00 h(ours) 00 m(inutes) 00 s(econds).

4-44