S4-07: UPS Power
Sets the capacity of the UPS.
■
S4-08: UPS Operation Speed Limit Selection
Determines how a speed limit should be applied to the Rescue Operation speed (S4-15) when operating from a UPS. The
drive calculates the appropriate speed limit based on the UPS capacity set in S4-07. This speed limit helps prevent voltage
saturation and motor stall during Rescue Operation.
Setting 0: Disabled
Setting 1: Enabled until Light Load Direction Search is complete
Setting 2: Enabled until stop
■
S4-12: DC Bus Voltage during Rescue Operation
Sets the DC bus voltage during Rescue Operation.
■
S4-13: Rescue Operation Power Supply Deterioration Detection Level
Determines at which level of backup power supply deterioration a PF5 fault is triggered. The following conditions will
trigger PF5:
• During Rescue Operation, DC bus voltage < [S4-12
× (S4-13 - 10%)]
• 100 ms after Rescue Operation has been triggered, the DC bus voltage does not rise above S4-12
× S4-13 before the
motor starts
■
S4-15: Speed Reference Selection at Rescue Operation
Selects the speed reference used for Rescue Operation.
Setting 0: The setting of parameter d1-25 is used as speed reference for Rescue Operation
Setting 1: The speed selected by digital inputs is used as speed reference
No.
Parameter Name
Setting Range
Default
S4-07
UPS Power
0.0 to 100.0 kVA
0.0 kVA
No.
Parameter Name
Setting Range
Default
S4-08
UPS Operation Speed Limit Selection
0 to 2
2
No.
Parameter Name
Setting Range
Default
S4-12
DC Bus Voltage during Rescue Operation
0 to 1150 V
0 V
No.
Parameter Name
Setting Range
Default
S4-13
Rescue Operation Power Supply Deterioration Detection Level
10 to 100%
80%
No.
Parameter Name
Setting Range
Default
S4-15
Speed Reference Selection for Rescue Operation
0, 1
0