beautypg.com

Control i/o configuration, Setting sink/source with input terminals sn and sp, 3 electrical installation – Yaskawa L1000E AC Drive CIMR-LE†A User Manual

Page 49

background image

3 Electrical Installation

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

49

El

ec

tr

ical

I

n

st

al

la

ti

o

n

3

Control I/O Configuration

Setting Sink/Source with Input Terminals SN and SP

Use the wire jumper between terminals SC and SP or SC and SN to select between Sink mode, Source mode or external
power supply for the digital inputs S1 to S8 as shown in

Table 16

(Default: Sink mode, internal power supply).

NOTICE: Damage to Equipment. Do not short terminals SP and SN. Failure to comply will damage the drive.

Table 16 Digital Input Sink / Source / External Power Supply Selection

Drive Internal Power Supply

(Terminal SN and SP)

External 24 Vdc Power Supply

Sinking Mode (NPN)

Sourcing Mode (PNP)

SC

S8

S7

24 Vdc

SP

SN

SC

S8

S7

24 Vdc

SP

SN

External

24 Vdc

SC

S8

S7

24 Vdc

SP

SN

SC

S8

S7

24 Vdc

SP

SN

External

24 Vdc