Switching Between LOCAL and REMOTE

LOCAL mode is when the drive is set to accept the Up/Down command from the digital operator keypad. REMOTE
mode is when the drive is set to accept the Up/Down command from an external device (via the input terminals or serial
communications, etc.).

Switch the operation between LOCAL and REMOTE using the LO/RE key on the digital operator or via a digital input.
This key is disabled with default settings, but can be enabled by setting parameter o2-01 to 1.

Note: 1. After selecting LOCAL, the LO/RE light will remain lit.

2. The drive will not allow the user to switch between LOCAL and REMOTE during run.

Using the LO/RE Key on the Digital Operator

Start-Up Flowcharts

This section covers basic setup for the drive, including Auto-Tuning procedures and corresponding flowcharts. Follow the
flowchart that matches the motor used in your application. Refer to

Types of Auto-Tuning on page 68

for details on the

types of Auto-Tuning.

Step

Display/Result

1.

Turn on the power to the drive. The initial display appears.

2.

Press

. The LO/RE light will light up. The drive is now in LOCAL.

To set the drive for REMOTE operation, press

again.

Flowchart

Purpose

Page

A

Installation, wiring, and basic steps required to setup the motor and elevator for operation

62

B

Auto-Tuning for induction motors

65

C

Auto-Tuning for PM motors

66

D

Encoder Offset Auto-Tuning

67

- MODE -

U1-01= 0.00%

U1-02= 0.00%
U1-03= 0.00A

DRV

Speed Ref(A1/A2)

Rdy

RSEQ
RREF

FWD

FWD/REV

YEA_

com-

LO
RE

F2

F1

ESC

RUN

STOP

ENTER

RESET

ALM

DIGITAL OPERATOR JVOP-180

- MODE -

U1-01= 0.00%

U1-02= 0.00%
U1-03= 0.00A

DRV

Speed Ref (OPR)

Rdy

LSEQ
LREF

FWD

YEA

_ c o

mm