Yaskawa L1000E AC Drive CIMR-LEA User Manual
Page 34
3 Electrical Installation
34
YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
Three-Phase 200 V Class
Table 8 Wire Gauge and Torque Specifications (Three-Phase 200 V Class)
Drive Model
Terminal
Recommended
Wire Size
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Screw
Size
Tightening Torque
N•m (lb.in.)
2A0018
R/L1, S/L2, T/L3
6.0
(10)
2.5 to 6.0
(14 to 10)
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
6.0
(10)
2.5 to 6.0
(14 to 10)
–, +1, +2
–
2.5 to 6.0
(14 to 10)
B1, B2
–
2.5 to 6.0
(14 to 10)
6.0
(10)
2.5 to 6.0
(14 to 10)
2A0022
R/L1, S/L2, T/L3
6.0
(10)
2.5 to 6.0
(14 to 10)
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
6.0
(10)
2.5 to 6.0
(14 to 10)
–, +1, +2
–
4.0 to 6.0
(12 to 10)
B1, B2
–
2.5 to 6.0
(14 to 10)
6.0
(10)
4.0 to 6.0
(12 to 10)
2A0031
R/L1, S/L2, T/L3
10
(8)
2.5 to 16
(12 to 6)
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
10
(8)
2.5 to 16
(12 to 6)
–, +1, +2
–
6.0 to 16
(10 to 6)
B1, B2
–
4.0 to 6.0
(12 to 10)
10
(8)
6.0 to 10
(10 to 8)
M5
2 to 2.5
(17.7 to 22.1)
2A0041
R/L1, S/L2, T/L3
16
(6)
2.5 to 16
(12 to 6)
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
16
(6)
2.5 to 16
(12 to 6)
–, +1, +2
–
16
(6)
B1, B2
–
4.0 to 6.0
(12 to 10)
10
(8)
6.0 to 10
(10 to 8)
M5
2 to 2.5
(17.7 to 22.1)
2A0059
R/L1, S/L2, T/L3
25
(4)
16 to 25
(6 to 4)
M6
4 to 6
(35.4 to 53.1)
U/T1, V/T2, W/T3
25
(4)
16 to 25
(6 to 4)
–, +1, +2
–
16 to 25
(6 to 4)
B1, B2
–
6.0 to 10
(10 to 6)
M5
2 to 2.5
(17.7 to 22.1)
16
(6)
10 to 16
(8 to 6)
M6
4 to 6
(35.4 to 53.1)