B parameter table – Yaskawa L1000E AC Drive CIMR-LEA User Manual
Page 212
B Parameter Table
212
YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
U3: Fault History
U4: Maintenance Monitors
No.
(Addr.)
Name
Description
Analog Output
Level
Unit
U3-01 to
U3-04
(90H to
93H
(800H to
803H))
First to 4th Most Recent
Fault
Displays the first to the fourth most recent faults.
No signal output
available
–
U3-05 to
U3-10
(804H to
809H)
5th to 10th Most Recent
Fault
Displays the fifth to the tenth most recent faults.
After ten faults have occurred in the drive, data for the oldest fault is deleted.
The most recent fault appears in U3-01, with the next most recent fault
appearing in U3-02. The data is moved to the next monitor parameter every
time a fault occurs.
No signal output
available
–
U3-11 to
U3-14
(94H to
97H
(80AH to
80DH))
Cumulative Operation
Time at 1st to 4th Most
Recent Fault
Displays the cumulative operation time when the first to the fourth most recent
faults occurred.
No signal output
available
1 h
U3-15 to
U3-20
(80EH to
813H)
Cumulative Operation
Time at 5th to 10th Most
Recent Fault
Displays the cumulative operation time when the fifth to the tenth most recent
faults occurred.
No signal output
available
1 h
No.
(Addr.)
Name
Description
Analog Output
Level
Unit
U4-01
(4CH, 98H,
99H)
Cumulative Operation
Time
Displays the cumulative operation time of the drive. The value for the
cumulative operation time counter can be reset in parameter o4-01. Use
parameter o4-02 to determine if the operation time should start as soon as the
power is switched on or only while the Up/Down command is present. The
maximum number displayed is 99999, after which the value is reset to 0.
No signal output
available
1 h
U4-03
(67H, 94H,
9BH)
Cooling Fan Operation
Time
Displays the cumulative operation time of the cooling fan. The default value
for the fan operation time is reset in parameter o4-03. This value will reset to 0
and start counting again after reaching 99999.
No signal output
available
1 h
U4-04
(7EH)
Cooling Fan
Maintenance
Displays main cooling fan usage time in as a percentage of its expected
performance life. Parameter o4-03 can be used to reset this monitor. The fan
should be replaced when this monitor reaches 90%.
No signal output
available
1%
U4-05
(7CH)
Capacitor Maintenance
Displays main circuit capacitor usage time in as a percentage of their expected
performance life. The capacitors should be replaced when this monitor reaches
90%. Parameter o4-05 can be used to reset this monitor.
No signal output
available
1%
U4-06
(7D6H)
Soft Charge Bypass
Relay Maintenance
Displays the soft charge bypass relay maintenance time as a percentage of its
estimated performance life. The soft charge relay should be replaced when this
monitor reaches 90%. Parameter o4-07 can be used to reset this monitor.
No signal output
available
1%
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_