beautypg.com

Yaskawa L1000E AC Drive CIMR-LE†A User Manual

Page 225

background image

C Standards Compliance

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

225

St

an

dar

d

s

Co

mplia

n

ce

C

Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum

allowable temperature of 75

°C 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed 40°C.

Closed-Loop Crimp Terminal Recommendations

Yaskawa recommends using closed-loop crimp terminals on all drive models. UL approval requires the use of UL Listed
crimp terminals when wiring the drive main circuit terminals on models 2A0106 to 2A0432 and 4A0056 to 4A0260. Use
only crimping tools as specified by the crimp terminal manufacturer. Yaskawa recommends crimp terminals made by JST
and Tokyo DIP (or equivalent) for the insulation cap.

Table 58

matches the wire gauges and terminal screw sizes with Yaskawa - recommended crimp terminals, tools, and

insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire gauge and screw size
for your drive model. Place orders with a Yaskawa representatives the Yaskawa sales department.

4A0140

R/L1, S/L2, T/L3

95

(3/0)

50 to 95

(1/0 to 4/0)

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

70

(2/0)

50 to 95

(1/0 to 4/0)

–, +1

50 to 95

(1/0 to 4/0)

+3

25 to 95

(3 to 4/0)

25

(4)

25

(4)

4A0188

R/L1, S/L2, T/L3

95

(4/0)

50 to 95

(1/0 to 4/0)

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

95

(4/0)

50 to 95

(1/0 to 4/0)

–, +1

35 to 95

(1 to 4/0)

+3

50 to 95

(1/0 to 4/0)

25

(4)

25 to 35

(4 to 2)

4A0225

R/L1, S/L2, T/L3

50

× 2P

(1

× 2P)

35 to 150

(2 to 300)

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

70

× 2P

(1/0

× 2P)

35 to 150

(2 to 300)

–, +1

50 to 150

(1 to 250)

+3

25 to 70

(3 to 3/0)

25

(4)

25 to 150

(4 to 300)

4A0260

R/L1, S/L2, T/L3

70

× 2P

(2/0

× 2P)

95 to 300

(1 to 600)

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

70

× 2P

(2/0

× 2P)

95 to 300

(1/0 to 600)

–, +1

70 to 300

(3/0 to 600)

+3

35 to 185

(1 to 325)

35

(2)

35 to 185

(2 to 350)

Drive Model

Terminal

Recommended

Wire Size

mm

2

(AWG, kcmil)

Wire Range

mm

2

(AWG, kcmil)

Screw

Size

Tightening Torque

N•m (lb.in.)