B parameter table – Yaskawa L1000E AC Drive CIMR-LEA User Manual
Page 213
B Parameter Table
YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
213
Pa
ra
me
te
r T
abl
e
B
U4-07
(7D7H)
IGBT Maintenance
Displays IGBT usage time as a percentage of the expected performance life.
The IGBTs should be replaced when this monitor reaches 90%. Parameter o4-
09 can be used to reset this monitor.
No signal output
available
1%
U4-08
(68H)
Heatsink Temperature
Displays the heatsink temperature.
10 V: 100
°C
1
°C
U4-09
(5EH)
LED Check
Lights all segments of the LED to verify that the display is working properly.
No signal output
available
–
U4-10
(5CH)
kWh, Lower 4 Digits
Monitors the drive output power. The value is shown as a 9 digit number
displayed across two monitor parameters, U4-10 and U4-11.
Example:
12345678.9 kWh is displayed as:
U4-10: 678.9 kWh
U4-11: 12345 MWh
No signal output
available
1 kWh
U4-11
(5DH)
kWh, Upper 5 Digits
No signal output
available
1 MWh
U4-13
(7CFH)
Peak Hold Current
Displays the highest current value that occurred during a ride.
No signal output
available
0.01 A
U4-14
(7D0H)
Peak Hold Output
Frequency
Displays the output frequency when the current value shown in U4-13
occurred.
No signal output
available
0.01 Hz
U4-16
(7D8H)
Motor Overload Estimate
(oL1)
Shows the value of the motor overload detection accumulator. 100% is equal
to the oL1 detection level.
10 V: 100%
0.1%
U4-17
(7D9H)
Drive Overload
Calculations (OL2)
Displays the level of the drive overload detection (oL2). A value of 100% is
equal to the oL2 detection level.
10 V = 100%
0.1%
U4-18
(7DAH)
Speed Reference
Selection Results
Displays the source for the speed reference as XY-nn.
X: indicates which reference is used:
1 = Reference 1 (b1-01)
Y-nn: indicates the reference source
0-01 = Digital operator
1-01 = Analog (terminal A1)
1-02 = Analog (terminal A2)
2-02 to 8 = Digital Inputs (d1-02 to 8)
3-01 = MEMOBUS/Modbus communications
4-01 = Communication option card
No signal output
available
–
U4-19
(7DBH)
Speed Reference from
MEMOBUS/Modbus
Comm.
Displays the speed reference provided by MEMOBUS/Modbus (decimal).
No signal output
available
0.01%
U4-20
(7DCH)
Speed Reference From
Option Card
Displays the speed reference input by an option card (decimal).
No signal output
available
0.01%
No.
(Addr.)
Name
Description
Analog Output
Level
Unit
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_