3 Electrical Installation

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

41

El

ec

tr

ical

I

n

st

al

la

ti

o

n

3

Cable Length Between Drive and Motor

Voltage drop along the motor cable may cause reduced motor torque when the wiring between the drive and the motor is
too long, especially at low frequency output. This can also be a problem when motors are connected in parallel with a
fairly long motor cable. Drive output current will increase as the leakage current from the cable increases. An increase in
leakage current may trigger an overcurrent situation and weaken the accuracy of the current detection.

Adjust the drive carrier frequency according to

Table 10

. If the motor wiring distance exceeds 100 m (328 ft.) because of

the system configuration, reduce the ground currents.

Refer to C6: Carrier Frequency on page 170

.

NOTICE: Equipment Hazard. Separate motor and/or braking circuit wiring (terminals, U/T1, V/T2, W/T3, +3, +2, +1,(-), B1, B2, from all

other wiring. Place motor wiring within its own conduit or cable tray with appropriate divider, and use shielded motor cable where

appropriate. Improper wiring practices could result in malfunction of drive due to electrical interference.

Table 10 Cable Length Between Drive and Motor

Note: When setting carrier frequency for drives running multiple motors, calculate cable length as the total wiring distance to all

connected motors.

Ground Wiring

Follow the precautions to wire the ground for one drive or a series of drives.

WARNING! Electrical Shock Hazard. Always use a ground wire that complies with technical standards on electrical equipment and

local installation regulations. Minimize the length of the ground wire. Improper equipment grounding may cause dangerous electrical

potentials on equipment chassis, which could result in death or serious injury.

WARNING! Electrical Shock Hazard. Be sure to ground the drive ground terminal (200 V class: Ground to 100

Ω or less, 400 V class:

Ground to 10

Ω or less). Improper equipment grounding may cause dangerous electrical potentials on equipment chassis, which could

result in death or serious injury.

NOTICE: Do not share the ground wire with other devices such as welding machines or large-current electrical equipment. Improper

equipment grounding could result in drive or equipment malfunction due to electrical interference.

NOTICE: When using more than one drive, ground multiple drives according to instructions. Improper equipment grounding could

result in abnormal operation of drive or equipment.

Refer to

Figure 22

when using multiple drives. Do not loop the ground wire.

Figure 22

Figure 22 Multiple Drive Wiring

Cable Length

50 m (164 ft.) or less

100 m (328 ft.) or less

Greater than 100 m (328 ft.)

Carrier Frequency

15 kHz or less

5 kHz or less

2 kHz or less

OK

OK

Not OK