B: application, B parameter table – Yaskawa L1000E AC Drive CIMR-LEA User Manual
Page 164
B Parameter Table
164
YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
A2: User Parameters
■
b: Application
Application parameters configure the source of the Up/Down command, timer functions, the Dwell function, the Droop
Control function, Energy Savings, and a variety of other application-related settings.
b1: Operation Mode Selection
A1-02
(102H)
Control Method Selection
0: V/f Control
2: Open Loop Vector Control
3: Closed Loop Vector Control
7: Closed Loop Vector Control for PM Motors
Default: 2
Min: 0
Max: 7
A1-03
(103H)
Initialize Parameters
0: No initialization
1110: User Initialize (parameter values must be stored using parameter o2-03)
2220: 2-wire initialization
5550: oPE04 error reset
Default: 0
Min: 0
Max: 5550
A1-04
(104H)
Password
When the value set into A1-04 does not match the value set into A1-05,
parameters A1-01 through A1-03, and A2-01 through A2-33 cannot be changed.
Default: 0000
Min: 0000
Max: 9999
A1-05
(105H)
Password Setting
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Settings 8 to 12 can only be selected from an LCD operator with software version 0102 or later. The version number of the LCD operator PRG
software is shown on the back of the LCD operator.
No.(Addr.)
Name
Description
Setting
A2-01 to
A2-32
(106 to
125H)
<5> Default setting is determined by the control mode (A1-02).
User Parameters 1 to 32
Parameters that were recently edited are listed here. The user can also select
parameters to appear here for quick access.
Min: A1-00
Max: o4-16
A2-33
(126H)
User Parameter Automatic
Selection
0: Parameters A2-01 through A2-32 are reserved for the user to create a list of
User Parameters.
1: Save history of recently viewed parameters. Recently edited parameters will
be saved to A2-17 through A2-32 for quick access.
Default: 1
Min: 0
Max: 1
No.(Addr.)
Name
Description
Setting
b1-01
(180H)
Speed Reference Selection
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option card
Default: 0
Min: 0
Max: 3
b1-02
(181H)
Up/Down Command
Selection
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option card
Default: 1
Min: 0
Max: 3
b1-03
(182H)
Stopping Method Selection
0: Ramp to stop
1: Coast to stop
4: Elevator Emergency Stop
Default: 0
Min: 0
Max: 4