YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

o2: Digital Operator Keypad Functions

o1-23

(174H)

HBB Non Display Select

Shows and hides HBB on the digital operator while the safety signal is being
input.
0: Show HBB
1: Hide HBB

Default: 0
Min: 0
Max: 1

<1> The control mode determines the selections available. In V/f Control, only settings 1 through 3 are permitted.

<2> Default setting is determined by the control mode (A1-02).

<5> This parameter appears when the drive displays user-set units (o1-03 = 3).

<6> Default setting and setting range changes when inches are selected for the length units (o1-12 = 1). The setting range becomes 3.70 to 78.00

inches, and the default becomes 15.70 inches.

No.

(Addr.)

Name

Description

Setting

o2-01

(505H)

<1> Parameter setting value is not reset to the default value when the drive is initialized.

LO/RE Key Function
Selection

0: Disabled
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.

Default: 0
Min: 0
Max: 1

o2-02

(506H)

STOP Key Function
Selection

0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.

Default: 0
Min: 0
Max: 1

o2-03

(507H)

User Parameter Default Value

0: No change.
1: Set defaults. Saves parameter settings as default values for a User
Initialization.
2: Clear all. Clears the default settings that have been saved for a User
Initialization.

Default: 0
Min: 0
Max: 2

o2-04

(508H)

<1>

Drive Model Selection

Enter the drive model. Setting required only if installing a new control board.

Default:
Determined by
drive capacity
Min: –
Max: –

o2-05

(509H)

Speed Reference Setting
Method Selection

0: ENTER key must be pressed to enter a speed reference.
1: ENTER key is not required. The speed reference can be adjusted using the up
and down arrow keys only.

Default: 0
Min: 0
Max: 1

o2-06

(50AH)

Operation Selection when
Digital Operator is
Disconnected

0: The drive continues operating if the digital operator is disconnected.
1: A fault is triggered (oPr) and the motor coasts to stop.

Default: 0
Min: 0
Max: 1

o2-09

(50DH)

Reserved

No.

(Addr.)

Name

Description

Setting

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_