B Parameter Table
198
YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
o2: Digital Operator Keypad Functions
o1-23
(174H)
HBB Non Display Select
Shows and hides HBB on the digital operator while the safety signal is being
input.
0: Show HBB
1: Hide HBB
Default: 0
Min: 0
Max: 1
<1> The control mode determines the selections available. In V/f Control, only settings 1 through 3 are permitted.
<2> Default setting is determined by the control mode (A1-02).
<5> This parameter appears when the drive displays user-set units (o1-03 = 3).
<6> Default setting and setting range changes when inches are selected for the length units (o1-12 = 1). The setting range becomes 3.70 to 78.00
inches, and the default becomes 15.70 inches.
No.
(Addr.)
Name
Description
Setting
o2-01
(505H)
<1> Parameter setting value is not reset to the default value when the drive is initialized.
LO/RE Key Function
Selection
0: Disabled
1: Enabled. LO/RE key switches between LOCAL and REMOTE operation.
Default: 0
Min: 0
Max: 1
o2-02
(506H)
STOP Key Function
Selection
0: Disabled. STOP key is disabled in REMOTE operation.
1: Enabled. STOP key is always enabled.
Default: 0
Min: 0
Max: 1
o2-03
(507H)
User Parameter Default Value
0: No change.
1: Set defaults. Saves parameter settings as default values for a User
Initialization.
2: Clear all. Clears the default settings that have been saved for a User
Initialization.
Default: 0
Min: 0
Max: 2
o2-04
(508H)
Drive Model Selection
Enter the drive model. Setting required only if installing a new control board.
Default:
Determined by
drive capacity
Min: –
Max: –
o2-05
(509H)
Speed Reference Setting
Method Selection
0: ENTER key must be pressed to enter a speed reference.
1: ENTER key is not required. The speed reference can be adjusted using the up
and down arrow keys only.
Default: 0
Min: 0
Max: 1
o2-06
(50AH)
Operation Selection when
Digital Operator is
Disconnected
0: The drive continues operating if the digital operator is disconnected.
1: A fault is triggered (oPr) and the motor coasts to stop.
Default: 0
Min: 0
Max: 1
o2-09
(50DH)
Reserved
–
–
No.
(Addr.)
Name
Description