3 Electrical Installation

42

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

Wiring the Main Circuit Terminal

WARNING! Electrical Shock Hazard. Shut off the power supply to the drive before wiring the main circuit terminals. Failure to comply

may result in death or serious injury.

Wire the main circuit terminals after the terminal board has been properly grounded.

Models 2A0018 through 2A0094 and 4A0009 through 4A0049 have a cover placed over the DC bus and braking circuit
terminals prior to shipment to help prevent miswiring. Use wire cutters to cut away covers as needed for terminals.

Figure 23

Figure 23 Protecting Cover to Prevent Miswiring (2A0059)

Main Circuit Connection Diagram

Refer to on page 26

when wiring terminals on the main power circuit of the drive.

WARNING! Fire Hazard. The braking resistor connection terminals are B1 and B2. Do not connect braking resistors to any other

terminals. Improper wiring connections could cause the braking resistor to overheat and cause death or serious injury by fire. Failure to

comply may result in damage to the braking circuit or drive.

Control Circuit Terminal Block Functions

Drive parameters determine which functions apply to the multi-function digital inputs (S3 to S8), multi-function digital
outputs (M1 to M6), multi-function photocoupler outputs (P1-C1, P2-C2), multi-function analog inputs (A1, A2), and
multi-function analog monitor output (FM, AM). The default setting is listed next to each terminal in

Figure 8

on page

24

.

NOTICE: Equipment Hazard. Improper equipment sequencing could shorten useful life of the electrolytic capacitors and circuit relays

of the drive. Refrain from switching an input contactor more often than once every 30 minutes. Normally the drive I/O should be used to

stop and start the motor.

WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being wired. Operating a drive

with untested control circuits could result in death or serious injury.

WARNING! Sudden Movement Hazard. Confirm the drive I/O signals and external sequence before starting test run. Failure to comply

may result in death or serious injury.

NOTICE: Frequently switching the drive power supply to stop and start the motor can damage the drive.

NOTICE: To get the full performance life out of the electrolytic capacitors and circuit relays, refrain from switching the drive power

supply off and on more than once every 30 minutes. Frequent use can damage the drive. Use the drive to stop and start the motor.

Note: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen over time. Improper wiring

practices could result in drive malfunction due to loose terminal connections.

A – Protecting Cover

A