4 Start-Up Programming

66

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

Flowchart C: Auto-Tuning for PM Motors

The flowchart below covers Auto-Tuning for permanent magnetic (PM) motors operating with Closed Loop Vector
Control for PM motors.

Figure 43 Auto-Tuning for PM Motors

<1> If an LED operator is used, the display shows “

”.

<2> If an LED operator is used, the display shows “

”.

Can the motor

rotate freely?

START

Set terminals H1-HC and H2-HC if Safe Disable function is used.

Is the motor data

sheet available?

FINISH

No

Yes

Select Stationary Auto-Tuning

T2-01 = 1.

Continue with encoder offset tuning.

Press the Run key on the digital operator

and wait until Auto-Tuning is finished.

Set the Baseblock input (H1-

= 8/9) if used.

Tuning

Successful?

Refer to

Remove the Fault/Alarm source and

repeat Auto Tuning.

Open terminals H1-HC and H2-HC if used during the normal sequence.

Open the motor contactor(s).

Open the Baseblock input (H1-

= 8/9) if used.

No

(Alarm or Fault code

displayed

Yes

(“Entry Accepted”

displayed

<2>

Enter the data in to T2-

parameters as

indicated on the display.

Select Motor Data Input

T2-01 = 0.

Enter the data in to T2-

parameters as

indicated on the display.

Press the Up key until “Tuning Ready” is

displayed.

<1>

Press the Up key until “Tuning Ready” is

displayed.

<1>

Close the motor contactor.

No

(Alarm or Fault code

displayed

・ Select Rotational Back EMF Constant Auto-Tuning T2-01=11.
・ Press the Up key.

Press the Run key on the digital operator

and wait until Auto-Tuning is finished.

Yes (Ropes removed)

No

Refer to

Flowchart D: PG Encoder Offset Auto-Tuning on page 67

.

Auto-Tuning Fault Detection

on page 138

.