B Parameter Table

178

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

F3: Digital Input Card (DI-A3)

F4: Analog Monitor Card (AO-A3)

No.(Addr.)

Name

Description

Setting

F3-01

(390H)

DI-A3 Option Card Input
Selection

0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
3: BCD, 1 Hz units
4: BCD, 0.1 Hz units
5: BCD, 0.01 Hz units
6: BCD customized setting (5 digit), 0.02 Hz units
7: Binary input
The unit and the setting range are determined by F3-03.
F3-03 = 0: 255/100% (-255 to +255)
F3-03 = 1: 40961/100% (-4095 to +4095)
F3-03 = 2: 30000/100% (-33000 to +33000)
When the digital operator units are set to be displayed in Hertz or user-set units
(o1-03 = 2 or 3), the units for F3-01 are determined by parameter o1-03.

Default: 0
Min: 0
Max: 7

F3-03

(3B9H)

DI-A3 Option Card Data
Length Selection

0: 8 bit
1: 12 bit
2: 16 bit

Default: 2
Min: 0
Max: 2

No.(Addr.)

Name

Description

Setting

F4-01

(391H)

Terminal V1 Function
Selection

Sets the monitor signal for output from terminal V1. Set this parameter to the last
three digits of the desired U -

monitor. Some U parameters are available

only in certain control modes.

Default: 102
Min: 000
Max: 999

F4-02

(392H)

Terminal V1 Gain

Sets the gain for voltage output via terminal V1.

Default: 100.0%
Min: -999.9%
Max: 999.9%

F4-03

(393H)

Terminal V2 Function
Selection

Sets the monitor signal for output from terminal V2. Set this parameter to the last
three digits of the desired U -

monitor. Some U parameters are available

only in certain control modes.

Default: 103
Min: 000
Max: 999

F4-04

(394H)

Terminal V2 Gain

Sets the gain for voltage output via terminal V2.

Default: 50.0%
Min: -999.9%
Max: 999.9%

F4-05

(395H)

Terminal V1 Bias

Sets the amount of bias added to the voltage output via terminal V1.

Default: 0.0%
Min: -999.9%
Max: 999.9%

F4-06

(396H)

Terminal V2 Bias

Sets the amount of bias added to the voltage output via terminal V2.

Default: 0.0%
Min: -999.9%
Max: 999.9%

F4-07

(397H)

Terminal V1 Signal Level
Selection

0: 0 to 10 V
1: -10 to 10 V

Default: 1
Min: 0
Max: 1

F4-08

(398H)

Terminal V2 Signal Level
Selection

Default: 1
Min: 0
Max: 1

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_