b2: Magnetic Flux Compensation

b4: Delay Timers

b6: Dwell Function

b7: Droop Control

b1-06

(185H)

Digital Input Reading

0: Input status is read once and processed immediately (for quick response).
1: Input is read twice and processed only if the status is the same in both readings
(robust against noisy signals).

Default: 1
Min: 0
Max: 1

b1-08

(187H)

Up/Down Command
Selection while in
Programming Mode

0: Up/Down command not accepted while in the Programming Mode.
1: Up/Down command accepted while in the Programming Mode.
2: Prohibit entering Programming Mode during run.

Default: 0
Min: 0
Max: 2

b1-14

(1C3H)

Phase Order Selection

0: U-V-W
1: U-W-V

Default: 0
Min: 0
Max: 1

<1> Maximum setting value is 1 in V/f Control and OLV Control.

No.(Addr.)

Name

Description

Setting

b2-08

(190H)

Magnetic Flux Compensation
Value

Sets the magnetic flux compensation as a percentage of the no-load current value
(E2-03).

Default: 0%
Min: 0%
Max: 1000%

No.(Addr.)

Name

Description

Setting

b4-01

(1A3H)

Timer Function On-Delay
Time

Used to set the on-delay and off-delay times for a digital timer output (H2-

=12). The output is triggered by a digital input programmed to H1-

=18.

Default: 0.0 s
Min: 0.0 s
Max: 3000.0 s

b4-02

(1A4H)

Timer Function Off-Delay
Time

Default: 0.0 s
Min: 0.0 s
Max: 3000.0 s

No.(Addr.)

Name

Description

Setting

b6-01

(1B6H)

Dwell Speed at Start

Parameters b6-01 and b6-02 set the speed to hold and the time to maintain that
speed at start.
Parameters b6-03 and b6-04 set the speed to hold and the time to maintain that
speed at stop.

Default: 0.0%
Min: 0.0%
Max: 100.0%

b6-02

(1B7H)

Dwell Time at Start

Default: 0.0 s
Min: 0.0 s
Max: 10.0 s

b6-03

(1B8H)

Dwell Speed at Stop

Default: 0.0%
Min: 0.0%
Max: 100.0%

b6-04

(1B9H)

Dwell Time at Stop

Default: 0.0 s
Min: 0.0 s
Max: 10.0 s

No.(Addr.)

Name

Description

Setting

b7-01

(1CAH)

Droop Control Gain

Sets the speed reduction gain applied at a torque reference of 100%. Set as a
percentage of motor base speed.

Default: 0.0%
Min: 0.0%
Max: 100.0%

b7-02

(1CBH)

Droop Control Delay Time

Used to adjust the responsiveness of Droop Control.

Default: 0.05 s
Min: 0.03 s
Max: 2.00 s

No.(Addr.)

Name

Description

Setting

All Modes

common

_

All Modes

common

_

All Modes

common

_

common

_

All Modes

All Modes

common

_

All Modes

common

_

common

_

CLV

CLV/PM

V/f

OLV

common

_

CLV

CLV/PM

V/f

OLV