b2: Magnetic Flux Compensation
b4: Delay Timers
b6: Dwell Function
b7: Droop Control
b1-06
(185H)
Digital Input Reading
0: Input status is read once and processed immediately (for quick response).
1: Input is read twice and processed only if the status is the same in both readings
(robust against noisy signals).
Default: 1
Min: 0
Max: 1
b1-08
(187H)
Up/Down Command
Selection while in
Programming Mode
0: Up/Down command not accepted while in the Programming Mode.
1: Up/Down command accepted while in the Programming Mode.
2: Prohibit entering Programming Mode during run.
Default: 0
Min: 0
Max: 2
b1-14
(1C3H)
Phase Order Selection
0: U-V-W
1: U-W-V
Default: 0
Min: 0
Max: 1
<1> Maximum setting value is 1 in V/f Control and OLV Control.
No.(Addr.)
Name
Description
Setting
b2-08
(190H)
Magnetic Flux Compensation
Value
Sets the magnetic flux compensation as a percentage of the no-load current value
(E2-03).
Default: 0%
Min: 0%
Max: 1000%
No.(Addr.)
Name
Description
Setting
b4-01
(1A3H)
Timer Function On-Delay
Time
Used to set the on-delay and off-delay times for a digital timer output (H2-
=12). The output is triggered by a digital input programmed to H1-
=18.
Default: 0.0 s
Min: 0.0 s
Max: 3000.0 s
b4-02
(1A4H)
Timer Function Off-Delay
Time
Default: 0.0 s
Min: 0.0 s
Max: 3000.0 s
No.(Addr.)
Name
Description
Setting
b6-01
(1B6H)
Dwell Speed at Start
Parameters b6-01 and b6-02 set the speed to hold and the time to maintain that
speed at start.
Parameters b6-03 and b6-04 set the speed to hold and the time to maintain that
speed at stop.
Default: 0.0%
Min: 0.0%
Max: 100.0%
b6-02
(1B7H)
Dwell Time at Start
Default: 0.0 s
Min: 0.0 s
Max: 10.0 s
b6-03
(1B8H)
Dwell Speed at Stop
Default: 0.0%
Min: 0.0%
Max: 100.0%
b6-04
(1B9H)
Dwell Time at Stop
Default: 0.0 s
Min: 0.0 s
Max: 10.0 s
No.(Addr.)
Name
Description
Setting
b7-01
(1CAH)
Droop Control Gain
Sets the speed reduction gain applied at a torque reference of 100%. Set as a
percentage of motor base speed.
Default: 0.0%
Min: 0.0%
Max: 100.0%
b7-02
(1CBH)
Droop Control Delay Time
Used to adjust the responsiveness of Droop Control.
Default: 0.05 s
Min: 0.03 s
Max: 2.00 s