B Parameter Table

194

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

n: Advanced Performance Set-Up

The n parameters are used to adjust more advanced performance characteristics such as speed feedback detection, Online
Tuning for motor line-to-line resistance, and PM motor control tuning.

n1: Hunting Prevention

n2: Speed Feedback Detection Control (AFR) Tuning

L8-62

(529H)

Operation Selection at Input
Phase Loss

Sets stopping method when a Input phase loss fault (PF) occurs. See parameter
L8-05.
0: Ramp to Stop - Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to Stop
2: Fast Stop - Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only - Drive continues operation.

Default: 1
Min: 0
Max: 3

L8-77

(61EH)

Oscillation Suppression

Used to suppress speed oscillations that occur with an unloaded motor and that
have the same frequency as the output frequency.

Default: 0
Min: -100
Max: 100

L8-88

(2F5H)

Safe Disable Operation Mode 0: Mode 0

1: Mode 1

Default: 1
Min: 0
Max: 1

L8-89

(B97H)

Current Monitoring Selection

Enables and disables the Current Monitoring function.
0: Disabled
1: Enabled

Default: 0
Min: 0
Max: 1

L8-99

(B98H)

Current Monitoring Level

Sets the current monitoring level as a percentage of the drive's rated current. Sets
the level of current used to monitor the status of the current (H2-

. = 5C)

when the Current Monitoring Selection (L8-89) is enabled and set to 1.

Default: 10.0 %
Min: 0.0 %
Max: 50.0 %

<1> Default setting is determined by the drive model (o2-04).

<3> Setting 3 available in V/f and OLV control only.

<4> Parameter setting value is not reset to the default value when the drive is initialized.

No.

(Addr.)

Name

Description

Setting

n1-08

(1105H)

Leakage Current Vibration
Control Selection

0: Method 1
1: Method 2
Parameter does not normally require adjustment.

Default: 0
Min: 0
Max: 1

No.

(Addr.)

Name

Description

Setting

n2-01

(584H)

Speed Feedback Detection
Control (AFR) Gain

Sets the internal speed feedback detection control gain in the automatic
frequency regulator (AFR).
If hunting occurs, increase the set value. If response is low, decrease the set
value.

Default: 1.00
Min: 0.00
Max: 10.00

n2-02

(585H)

Speed Feedback Detection
Control (AFR) Time
Constant 1

Sets the time constant used for speed feedback detection control (AFR).

Default: 50 ms
Min: 0 ms
Max: 2000 ms

n2-03

(586H)

Speed Feedback Detection
Control (AFR) Time
Constant 2

Sets the AFR time constant to be used during regen.

Default: 750 ms
Min: 0 ms
Max: 2000 ms

No.

(Addr.)

Name

Description

Setting

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

common

_

CLV

CLV/PM

V/f

OLV

common

_

CLV

CLV/PM

V/f

OLV

common

_

CLV

CLV/PM

V/f

OLV