3 Electrical Installation

44

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

Output Terminals

Table 12

lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function

output.

Note: Multi-function relay output terminals are rated at a minimum of 10 mA. If less than 10 mA is required, use the photocoupler

outputs (P1-C1, P2-C2). Using the wrong current output level may cause the output to malfunction when the terminal is activated.

Table 12 Control Circuit Output Terminals

Figure 24

Figure 24 Connecting a Suppression Diode

Serial Communication Terminals

Table 13 Control Circuit Terminals: Serial Communications

Type

<1> Refrain from assigning functions to terminals M1 thru M6 that involve frequent switching, as doing so may shorten relay performance life.

Switching life is estimated at 200,000 times (assumes 1 A, resistive load).

<2> Connect a suppression diode as shown in

Figure 24

when driving a reactive load such as a relay coil. Make sure the diode rating is greater than

the circuit voltage.

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Fault Relay

MA

N.O.

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA

MB

N.C. output

MC

Fault output common

Multi-Function
Relay Output

<1>

M1

Multi-function relay output 1 (Brake release
command)

Contact relay output
30 Vdc, 10 mA to 1 A
250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA

M2
M3

Multi-function relay output 2 (Output contactor close
command)

M4
M5

Multi-function relay output 3 (Drive ready)

M6

Multi-Function
Photocoupler
Output

P1

Photocoupler output 1 (During Frequency output)

48 Vdc, 2 to 50 mA

<2>

C1

P2

Photocoupler output 2 (Not Used/Through Mode)

C2

Monitor Output

FM

Analog monitor output 1 (Output speed)

-10 to +10 Vdc or 0 to +10 Vdc

AM

Analog monitor output 2 (Output current)

AC

Monitor common

0 V

Safety Monitor
Output

DM+ Safety monitor output

Outputs status of Safe Disable function. Closed when both Safe
Disable channels are closed. Up to +48 Vdc 50 mA

DM-

Safety monitor output common

A – External power, 48 V max.

C – Coil

B – Suppression diode

D – 50 mA or less

Type

<1> Enable the termination resistor in the last drive in a MEMOBUS network by setting DIP switch S2 to the ON position.

No.

Signal Name

Function (Signal Level)

MEMOBUS/Modbus
Communication

<1>

R+

Communications input (+)

MEMOBUS/Modbus communication: Use
an RS-485 or RS-422 cable to connect the
drive.

RS-485/422
MEMOBUS/Modbus
communication
protocol
115.2 kbps (max.)

R-

Communications input (-)

S+

Communications output (+)

S-

Communications output (-)

IG

Shield ground

0 V

A

B

C

D