Yaskawa L1000E AC Drive CIMR-LEA User Manual
Page 38
3 Electrical Installation
38
YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
4A0039
R/L1, S/L2, T/L3
16
(6)
6.0 to 16
(10 to 6)
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3
10
(8)
6.0 to 16
(10 to 6)
–, +1, +2
–
16
(6)
B1, B2
–
6.0 to 10
(10 to 8)
M5
2.7 to 3.0
(23.9 to 26.6)
16
(6)
6.0 to 16
(10 to 6)
M6
4 to 6
(35.4 to 53.1)
4A0049
R/L1, S/L2, T/L3
16
(6)
16 to 25
(6 to 4)
M6
4 to 6
(35.4 to 53.1)
U/T1, V/T2, W/T3
16
(6)
16 to 25
(6 to 4)
–, +1, +2
–
16 to 25
(6 to 4)
B1, B2
–
6.0 to 10
(10 to 8)
M5
2 to 2.5
(17.7 to 22.1)
16
(6)
10 to 16
(8 to 6)
M6
4 to 6
(35.4 to 53.1)
4A0056
R/L1, S/L2, T/L3
25
(4)
6.0 to 50
(10 to 1/0)
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
25
(4)
6.0 to 50
(10 to 1/0)
–, +1
–
16 to 35
(6 to 1)
B1, B2
–
10 to 16
(8 to 4)
16
(6)
10 to 16
(8 to 6)
4A0075
R/L1, S/L2, T/L3
35
(3)
6.0 to 70
(10 to 3/0)
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
35
(3)
6.0 to 70
(10 to 3/0)
–, +1
–
25 to 35
(4 to 1)
B1, B2
–
16 to 25
(6 to 3)
16
(6)
16
to 25
(6)
4A0094
R/L1, S/L2, T/L3
35
(2)
16 to 120
(6 to 250)
M8
9 to 11
(79.7 to 97.4)
U/T1, V/T2, W/T3
50
(1)
16 to 120
(6 to 250)
–, +1
–
25 to 50
(3 to 1/0)
+3
–
16 to 50
(6 to 1/0)
25
(4)
16 to 25
(6 to 4)
Drive Model
Terminal
Recommended
Wire Size
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Screw
Size
Tightening Torque
N•m (lb.in.)