A specifications, Three-phase 200 v class drives, Aspecifications – Yaskawa L1000E AC Drive CIMR-LEA User Manual
Page 159
A Specifications
YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
159
S
p
ec
ifi
c
at
ions
A
A
Specifications
◆ Three-Phase 200 V Class Drives
Table 52 Power Ratings (Three-Phase 200 V Class)
Item
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> DC is not available for UL standards.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency can be set up to 8 kHz while keeping this current rating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be set up to 5 kHz while keeping this current rating. Higher carrier frequency settings require derating.
Specification
CIMR-LE2A
0018 0022 0031 0041 0059 0075 0094 0106 0144 0181 0225 0269 0354 0432
Maximum Applicable Motor Capacity kW
(HP)
3.7
(5)
5.5
(7.5)
7.5
(10)
11.0
(15)
15.0
(20)
18.5
(25)
22.0
(30)
30.0
(40)
37.0
(50)
45.0
(60)
55.0
(75)
75.0
(100)
90.0
(125)
110.0
(150)
Input
Input Current (A)
15.6 18.9
28
37
52
68
80
82
111
136
164
200
271
324
Rated Voltage
Rated Frequency
Three-phase 200 to 240 Vac 50/60 Hz/270 to 340 Vdc
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±5%
Input Power (kVA)
7.8
9.5 14 18 27 36 44 37 51 62 75 91
124
148
Output
Rated Output Capacity (kVA)
5.3
6.7
9.5
12.6
17.9
23
29
32
44
55
69
82
108
132
Rated Output Current
(3 minutes, 50% ED) (A)
17.5
21.9
31.3
41.3
58.8
75.0
93.8
106.3
143.8
181.3
225.0
268.8
353.8
432.5
Overload Tolerance
133% of rated output current for 30 s
Carrier Frequency
User adjustable between 2 and 15 kHz
User adjustable between 2 and 10
kHz
Maximum Output Voltage (V)
Three-phase 200 to 240 V (proportional to input voltage)
Maximum Output Speed (Hz)
120 Hz (user-set)