4 start-up programming, Refer to figure 58 for a wiring diagram, Wiring – Yaskawa L1000E AC Drive CIMR-LEA User Manual
Page 107
4 Start-Up Programming
YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
107
St
ar
t-
Up
Pr
og
ra
m
m
in
g
4
WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Never remove or install option cards or
attempt to replace the cooling fan while the drive is switched on. Make sure that the drive and all devices connected to the drive have
been shut off prior to performing and type of maintenance or wiring. After shutting off the power, wait for at least the amount of time
specified on the drive before touching any components or perform wiring. The internal capacitor remains charged even after the power
supply is turned off.
NOTICE: Be sure to thoroughly read the instructions for wiring and magnetic contactor sequence described in this section before
setting up the drive for Rescue Operation. Failure to follow these instructions can damage the drive.
NOTICE: Refrain from using Rescue Operation for extend periods of time. Rescue Operation uses a low DC bus voltage, which can
cause the cooling fan to shut off temporarily during Rescue Operation. Continuing to operate under these conditions can trigger an
overheat fault and damage the drive.
NOTICE: Install the inrush current suppression circuit outside the drive if the DC bus battery voltage is lower than 190 Vdc for 200 V
class drives of models CIMR-LE2A0269 to 2A0432, 380 Vdc for 400 V class drives of models CIMR-LE4A0188 to 4A0260. Failure to
comply will cause the soft-charge bypass relay to remain open and result in damage to the drive.
Using a Single-Phase, 230 Vac UPS (Uninterruptable Power Supply)
Follow the instructions when using a single-phase 230 V UPS for Rescue Operation. A 230 V UPS can be used for 200 V
and 400 V class drives.
Wiring
for a wiring diagram.
Figure 51
Figure 58 Using a Single-Phase 230 V UPS
-
L1000A
Magnetic Contactor Sequence
H1-
غغ = 55
(Rescue Operation)
sine wave
230 Vac
single-phase
H1-
غغ = 55
(Rescue Operation)
L1
L2
L3
N
R/L1
S/L2
T/L3
CN19
S
3
to S
8
1
4
SC
+1
+2
B2
W/T3
V/T2
U/T1
Magnetic
Contactor B
Magnetic
Contactor A
UPS
Magnetic Contactor B
Magnetic Contactor A
Elevator
control
system
Control
circuit
Power supply