Connect to a pc, 3 electrical installation – Yaskawa L1000E AC Drive CIMR-LEA User Manual
Page 50
3 Electrical Installation
50
YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
■
Sinking/Sourcing Mode Selection for Safe Disable Inputs
Use jumper S3 on the terminal board to select between Sink mode, Source mode or external power supply for the Safe
Disable inputs H1 and H2 as shown in
(Default: Sink mode, internal power supply).
Table 17 Safe Disable Input Sink / Source / External Power Supply Selection
◆ Connect to a PC
This drive is equipped with a USB port (type-B).
The drive can connect to a USB port on a PC using a USB 2.0, AB-type cable (sold separately). After connecting the
drive to a PC, Yaskawa DriveWizard Plus software can be used to monitor drive performance and manage parameter
settings. Contact Yaskawa for more information on DriveWizard Plus.
Download and install the USB driver before connecting L1000 to a PC with the USB cable.
To obtain the driver and software of USB Copy Unit, CopyUnitManager and DriveWizardPlus, access these sites:
U.S.A: http://www.yaskawa.com
Other areas: contact a Yaskawa representative.
Figure 30
Figure 30 Connecting to a PC (USB)
Drive Internal Power Supply
External 24 Vdc Power Supply
Sinking Mode
Sourcing Mode
24 Vdc
H1
H2
HC
Jumper S3
24 Vdc
H1
H2
HC
External
24 Vdc
Jumper S3
24 Vdc
H1
H2
HC
Jumper S3
24 Vdc
H1
H2
HC
External
24 Vdc
Jumper S3
PC
(Type-B)
(Type-A)
USB Cable
(Type-AB)
Y E