C standards compliance, Ul standards, For information – Yaskawa L1000E AC Drive CIMR-LEA User Manual
Page 219: Cstandards compliance, Ul standards compliance
C Standards Compliance
YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
219
St
an
dar
d
s
Co
mplia
n
ce
C
C
Standards Compliance
◆ UL Standards
■
UL Standards Compliance
The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing
and evaluation, and determined that their stringent standards for product safety have been met. For a product to receive
UL certification, all components inside that product must also receive UL certification.
Figure 94
Figure 103 UL/cUL Mark
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. To ensure continued
compliance when using this drive in combination with other equipment, meet the following conditions:
Installation Area
Do not install the drive to an area greater than pollution severity degree 2 (UL standard).
Ambient Temperature
IP00 enclosure with top protective cover: -10 to +40
°C
IP00 enclosure: -10 to +50
°C
Main Circuit Terminal Wiring
Yaskawa recommends using closed-loop crimp terminals on all drive models. UL/cUL approval requires the use of UL
Listed closed-loop crimp terminals when wiring the drive main circuit terminals on models 2A0106 to 2A0432 and
4A0056 to 4A0260. Use only the tools recommended by the terminal manufacturer for crimping.
The wire gauges listed in
are Yaskawa recommendations. Refer to local codes for proper wire
gauge selections.
Note: The mark indicates the terminals for protective ground connection. (as defined in IEC60417-5019)
Grounding impedance;
200 V: 100
Ω or less
400 V: 10
Ω or less
Table 56 Wire Gauge and Torque Specifications (Three-Phase 200 V Class)
Drive Model
Terminal
Recommended
Wire Size
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Screw
Size
Tightening Torque
N•m (lb.in.)
2A0018
R/L1, S/L2, T/L3
6.0
(10)
2.5 to 6.0
(14 to 10)
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
6.0
(10)
2.5 to 6.0
(14 to 10)
–, +1, +2
–
2.5 to 6.0
(14 to 10)
B1, B2
–
2.5 to 6.0
(14 to 10)
6.0
(10)
2.5 to 6.0
(14 to 10)