Yaskawa L1000E AC Drive CIMR-LEA User Manual
Page 36
3 Electrical Installation
36
YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide
Note: When connecting peripheral devices and options to the terminals –, +1, +3, B1, and B2, refer to the instruction manuals for each
device. For more information, contact Yaskawa or your nearest sales representative.
2A0225
R/L1, S/L2, T/L3
70
× 2P
(1/0
× 2P)
70 to 95
(1/0 to 4/0)
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3
70
× 2P
(1/0
× 2P)
70 to 95
(1/0 to 4/0)
–, +1
–
50 to 95
(1 to 4/0)
+3
–
70 to 95
(1/0 to 4/0)
25
(4)
25 to 50
(4 to 1/0)
2A0269
R/L1, S/L2, T/L3
95
× 2P
(3/0
× 2P)
95 to 150
(3/0 to 300)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
95
× 2P
(3/0
× 2P)
95 to 150
(3/0 to 300)
–, +1
–
95 to 150
(3/0 to 300)
+3
–
35 to 150
(2 to 300)
M10
18 to 23
(159 to 204)
35
(3)
35 to 150
(2 to 300)
M12
32 to 40
(283 to 354)
2A0354
R/L1, S/L2, T/L3
120
× 2P
(4/0
× 2P)
95 to 150
(3/0 to 300)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
120
× 2P
(4/0
× 2P)
95 to 150
(3/0 to 300)
–, +1
–
95 to 150
(3/0 to 300)
+3
–
95 to 150
(3/0 to 300)
M10
18 to 23
(159 to 204)
35
(2)
35 to 150
(2 to 300)
M12
32 to 40
(283 to 354)
2A0432
R/L1, S/L2, T/L3
150
× 2P
(250
× 2P)
95 to 300
(4/0 to 600)
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3
185
× 2P
(300
× 2P)
95 to 300
(4/0 to 600)
–, +1
–
120 to 300
(250 to 600)
+3
–
70 to 300
(3/0 to 600)
M10
18 to 23
(159 to 204)
50
(1)
120 to 240
(1 to 350)
M12
32 to 40
(283 to 354)
Drive Model
Terminal
Recommended
Wire Size
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Screw
Size
Tightening Torque
N•m (lb.in.)