4 Start-Up Programming

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

121

St

ar

t-

Up

Pr

og

ra

m

m

in

g

4

7.

Use a Phillips screwdriver to fasten the screw that holds the CN19 connector cover in place.

NOTICE: Use the screw provided to fasten the connector cover into place. Using a different screw may damage the internal drive

components.

Figure 70

Figure 77 Reattaching the CN19 Connector Cover

Figure 71

Figure 78 Drive and Battery CN19 Connection Complete

Rescue Operation Torque Limit

The Torque Limit During Rescue Operation is set in parameter S4-05. After Rescue Operation is complete, the drive
utilizes to the torque limits set in the L7 parameters.

Light Load Direction Search Function

Light Load Direction Search can be used to automatically perform Rescue Operation in the direction with the lower load.
It can help to minimize the amount of power required by the backup power supply required for Rescue Operation. Light
Load Direction Search can be set so that it is automatically performed when Rescue Operation is started. To enable Light
Load Direction Search set parameter S4-01 = 1.

When Light Load Direction Search is enabled the drive first runs in the up and then in the down direction, each for the
time set to S4-03. It then compares the load condition of both operations and travels to the next floor using the lighter load
condition direction. The speed reference used for Light Load Direction Search can be set in parameter S4-04.